IM-P693-06
EMM Issue 1
13
LCS3050 Low Water Level Switch for two probes
5.1 Factory setting
-
De-energizing delay: 3 sec (factory set).
-
Configuration: Operation with two level probes LP40. S1/S2 of code switches 4 and 5 set to OFF.
Danger
The terminal strips of the LCS3050 are live during operation. This presents the
danger of electric shock!
Always cut off power supply to the equipment before mounting, removing or
connecting the terminal strips!
Changing the function of the level switch
If only one probe is used for operation (e. g. in case of emergency operation) change the settings as follows:
-
Switch off supply voltage.
-
Unscrew the right and left fixing screws 3 and remove the lower terminal strip 2, Fig. 2.
-
Depending on which probe shall be deactivated, set S1/S2 of code switches 4 and 5 to ON.
-
Attach lower terminal strip and fasten fixing screws.
-
Apply supply voltage, equipment is re-started.
4
Toggle switch, white
5
Toggle switch, white
Code switch 4
Code switch 5
S 1
S2
S 1
S2
Level probe 1 activated
OFF
OFF
Level probe 1 deactivated
ON
ON
Level probe 2 activated
OFF
OFF
Level probe 2 deactivated
ON
ON
Note
If only one level probe is switched on, only the LEDs for power and alarm of the
corresponding channels will be illuminated.
5. Commissioning