SP160 SERIES 7M MULTI-TAPER CV FACTORS
PLEASE CONTACT THE FACTORY FOR INFORMATION ON 7MR O-RING SEAT OPTIONS.
DATA IS BASED ON WATER AT 70°F
MODULATING VALVES
1"
1 1/2"
2"
2 1/2"
3"
0
20
40
60
80
100
120
10
20
30
40
50
60
70
80
90
100
Cv F
act
or
Valve Stroke
CV VS. % STROKE
VALVE
SIZE
OPERATING RANGE
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
1.0”
0.25
0.75
1.00
1.25
1.875
3.00
4.00
5.00
6.50
12.00
1.5”
0.50
1.00
2.00
3.00
4.00
6.50
6.80
8.30
9.30
14.30
2.0”
1.90
3.20
7.30
11.90
14.60
16.90
20.00
24.20
29.20
33.70
2.5”
2.00
3.90
8.70
14.80
20.40
26.00
31.00
37.00
47.00
53.50
3.0”
4.90
10.00
18.50
24.00
31.00
39.60
56.00
72.00
87.40
110.00