7
alligator clip of the test leads connected. The indicator should read
00.0
Ω
. When the leads are not connected the display will read
infinity indicated by “
OL
”. This will ensure that test lead are under
working condition.
2-4 Rotary Switch positions
Turn the Tester on by selecting any measurement
Lift
<
1000v,500v,250v,125v (4000M
Ω
)
OFF 400
Ω
/BZ, 1000VDC,750VAC
>
Right
2-5 Buttons and a display Indicators
a). Button
HOLD/MAX.MIN :
Instant-pressing the
“
HOLD
”
button the 1st time,
the current values will be hold in the primary display., but it will return
in the 2nd pressing ; pressing 2 seconds ,it will enter directly into the
“
MAX
”
status, and one another instant-pressing will switch to the
“
MIN
”
, if instant-pressing once more, it will recycle ,but exit if
pressing 2 seconds again.
LOCK :
In the insulation resistance testing function ,press the
“
LOCK
”
button ,and then push down the
“
TEST
”
key, it will occur the
high-voltage and enter the insulation resistance testing status. Press
the
“
TEST
”
button once more ,it will shutoff the high-voltage and exit
from the insulation resistance testing status.
TEST :
In the insulation resistance testing function ,pressing and
holding the
“
TEST
”
button, The meter will bring high-voltage, and
enter into the insulation resistance testing, being free from the
“
TEST
”
, it will cutoff the high-voltage and exit form the insulation
resistance testing.
ZERO/LIGHT :
Iinstant-pressing
the “
ZERO/LIGHT
”
button in the 1st
time, the current values in the primary display will be set
zero,(mainly used for 400
Ω
, the low resistance testing), ,it will return