Chapter 3
Using the Function Menu
3–7
The P-Port option on the Function Menu lets you manually set the RS-232
printer port parameters. Normally these parameters are set automatically
from the DPS programming software when an application is downloaded.
This menu options is only valid for versions that have a printer port.
Select P-Port [2] from the Function Menu.
1 C-Port
5 Special
2 P-Port
6 Term
3 Clk/Cal
7 Test
4 Reset
8 Other
This menu displays:
1 Baud Rate
5 L/Feed
2 Data Bits
6 Penable
3 Parity
7 Exit
4 Hndshk
Baud Rate
Selecting Baud Rate [1] displays the current baud rate.
Select Baud Rate:
Baud Rate
9600
”NEXT” To Change
”ENTER” To Select
Press [NEXT] to toggle through the options: 300, 1200, 2400, 4800, 9600,
19200, 38400. Press [
] to select a new rate.
Data Bits
Selecting Data Bits [2] displays the current setting.
Select Bit Counts:
Bits
8
”NEXT” To Change
”ENTER” To Select
Press [NEXT] to change between 7 or 8 bits. Press [
] to select a setting.
Setting Printer
Port Parameters