Special Controller Functions
Appendix C
C–7
To read/write the contents of controller Timer files:
1. Select item 1 from the Special Menu to access the P–A/D function.
You are prompted for a file type:
Select file type:
(O)Output
PREV/NEXT To Scroll
ENTER To Select
2. Press [NEXT] and [PREV] keys to scroll through the file types.
Select (T)Timer and press [
].
You are prompted for a timer file number:
Select File Number
4
Press ENTER
File Number
4
Word Address: 0
File Number:
4
Element Addr: 0
PLC-5 DF1
Operating System
DH485
Operating System
Select File Number
4
Press ENTER
3. Enter the timer file number and word or element address.
You are shown the timer data:
T004:000
Acc 00000
Pre 00000
EN
TT
DN
0
0
0
Bits
(Enable,
Timer Timing,
Done)
4. To change the Acc and Pre values or element address, move the cursor to
the data field using the [PREV] or [NEXT] keys. Enter the new data.
!
ATTENTION: Do not send negative timer values to the
controller. Negative timer values can cause a controller fault.
5. Press the [
] key to enter new accumulator or preset values to the
displayed timer address.
6. Pressing the [PREV MENU] key at any time returns to the P–A/D file
select menu.
Reading / Writing Controller
Timer Files