Product Overview
TM40/40UFL Rev. (Al), February 2019
21
TR CU/EAC, page 23
2.3.6.1
ATEX, IECEx
The 40/40UFL Flame Detector is certified to:
•
ATEX per SIRA 07ATEX1250X and IECEx per IECEx SIR 07.0085X
Ex II 2G D
Ex db eb op is IIC T4 Gb
Ex tb op is IIIC T96°C Db
(
–55°C ≤ Ta ≤
+75°C)
Or
•
Ex II 2G D
Ex db eb op is IIC T4 Gb
Ex tb op is IIIC T106°C Db
(
–55°C ≤ Ta ≤ +85°C)
The accessories, Tilt Mount P/N 40/40-001, Weather Cover P/N 777163 and P/N
777268, Duct Mount P/N 777670, and Air Shield P/N 777650 are included in the
approval.
This product is suitable for use in hazardous zones 1 and 2 with IIC gas group
vapors present, and zones 21 and 22 with IIIC dust type present.
2.3.6.2
FM
The 40/40UFL Flame Detector is approved to FM Explosion Proof and FM
Functionality approved per FM3260:
•
Class I, Division 1, Groups B, C, and D, T5 Ta = 185°F/85°C.
•
Dust Ignition Proof
–
Class II/III Division 1, Groups E, F, and G.
•
Ingress Protection
–
IP67, IP66, NEMA 250 Type 6P.
•
For more details see Report Project ID3029553.
2.3.6.3
SIL-2 (TÜV)
The 40/40UFL Flame Detector is approved to SIL-2 requirement per IEC 61508.4,
Chapter 3.5.12.
The alert condition according to SIL-2 can be implemented by:
•
Alert signal via 0
–
20mA current loop.
Or
•
Alert signal via alarm relay and fault relay.
•
For more details, see Test Report No. 968/EZ 348.
2.3.6.4
EN54-10
The 40/40UFL Flame Detector is approved per EN54-10 and CPD.
•
The detector has been tested and approved per EN54-10 by VdS (Germany).