Product Overview
TM40/40UFL Rev. (Al), February 2019
45
3.9.3
Function Setup
You can select the desired functions as detailed in Table 14.
Table 14: Functions
Function
Setting
Alarm Latch
Yes
: Enable alarm latching.
No
: Disable alarm latching (default).
Auxiliary Relay
*
Yes
: Activate auxiliary relay at warning level.
No
: Activate Auxiliary Relay at Alarm level (default).
Automatic BIT
Yes
: Perform automatic (default).
No
: No BIT.
EOL
*
Yes
: Auxiliary relay is used as End-of-Line.
No
: Auxiliary relay operates in accordance with Functions
2 and 5 (default).
Only available in Models 40/40UFI-4XXXX and 5XXXX
3.9.4
Heated Optics
The heated optics can be defined as one of the following modes:
•
Heated Mode
•
Off
: Not operated
•
On
: Continuously
•
Auto
: Per temperature change
In Auto mode, the default Heat On setting is 41°F/5°C. Heating stops when the
temperature is 27°F/15°C above the start temperature.
You can define the start temperature below which the window will be heated. The
temperature can be defined between 32
–
86°F / 0
–
30°C.