
S
PECTRA
1759EX
17
5.7
ZONE PARTITION ASSIGNMENT
Sections [001] to [015]: Zones 1 to 15
The control panel provides the option of partitioning the security system into
two completely independent systems. As demonstrated in Figure 5-1 on
page 15, sections [001] to [015] represent zones 1 through 15 respectively,
where the second digit in each of these sections represents the zone's
partition assignment. The zone is assigned to Partition 1 if second digit =
1
,
Partition 2 if second digit =
2
, or both partitions is second digit =
3
. For more
details, refer to
5.8
ZONE OPTIONS
As demonstrated in Figure 5.1, sections [001] to [015] represent zones 1
through 15 respectively. After entering the first two digits, select one or
more of the following Zone Options by using the Multiple Feature Select
Programming Method
(see page 8):
5.8.1
A
UTO
Z
ONE
S
HUTDOWN
Sections [001] to [015] = Zones 1 to 15
Option [1] OFF = Auto Zone Shutdown Disabled
Option [1] ON
= Auto Zone Shutdown Enabled for
selected zone (default)
If, in a single armed period, the number of alarms generated by a
zone with the Auto Zone Shutdown option enabled exceeds the
number defined by the Auto Zone Shutdown Counter, the control
panel will no longer generate an alarm for that zone. To program
the Auto Zone Shutdown Counter, key in the desired limit
(000=Disabled, 001 to 015, Default = 5) into section [089]. The
Auto Zone Shutdown Counter resets every time the partition that
is assigned to the corresponding zone is armed.
5.8.2
B
YPASS
Z
ONES
Sections [001] to [015] = Zones 1 to 15
Option [2] OFF = Bypass Zone Disabled
Option [2] ON
= Selected Zone is Bypass Enabled
(default)
When a user utilizes the Bypass Programming feature (see page 45), only zones with the Bypass option enabled can
be programmed as bypassed.
Do not program a Fire Zone with the Bypass option, as the control panel will never bypass Fire Zones.
5.8.3
S
TAY
Z
ONES
Sections [001] to [015]: Zones 1 to 15
Option [3] OFF = Stay Zone Disabled (default)
Option [3] ON
= Selected Zone is Stay Enabled
Zones with the Stay option enabled will be bypassed when the system is
Stay Armed
Do not program a Fire Zone with the Stay option, as the control panel will never bypass Fire Zones
when Stay Arming.
5.8.4
A
LARM
T
YPES
Sections [001] to [015]: Zones 1 to 15
[4]
OFF /
[5]
OFF:
Audible Steady
(default)
When the conditions for an alarm have been met, the control panel can transmit the appropriate Zone Alarm report
code (see page 29) and provides a steady output for any bells or sirens connected to the control panel’s bell output.
[4]
OFF /
[5]
ON:
Audible Pulsed Alarm
When the conditions for an alarm have been met, the control panel can transmit the appropriate Zone Alarm report
code (see page 29) and provides a pulsed output (see Figure 5.2 on page 16) for any bells or sirens connected to the
control panel’s bell output.
[4]
ON /
[5]
OFF:
Silent Alarm
When the conditions for an alarm are met, the control panel can transmit the appropriate Zone Alarm report code (see
page 29) and will not activate the control panel’s bell output. The appropriate
ARM
or
STATUS
LED on the keypads will
flash to indicate an alarm and the user will still have to disarm the system.
Figure 5.3: Delayed 24Hr. Fire Zone
Содержание 1759ex
Страница 1: ...1759EX V1 0 REFERENCE INSTALLATION MANUAL 433MHZ 868MHZ 1759EX...
Страница 2: ......
Страница 55: ......