Space-Ray Ultra 14 Скачать руководство пользователя страница 9

Page 7 of 

20

3.1.6

Minimum clearance from combustibles.

Table 11

MODEL

HORIZONTAL

60

0

ABOVE

BELOW

SIDE

FRONT

BACK

FRONT

BACK

Ultra 7 & 7/3.5

670

670

950

225

1000

1340

670

Ultra 14 & 14/7

1000

1000

2000

335

1000

2840

1255

Ultra 21 & 21/10.5

1365

1365

2480

365

1090

3080

1365

Ultra 28 & 28/14

1510

1510

2590

405

1210

3680

1670

Ultra 42 & 42/21

2260

2260

3890

500

1505

5520

2510

3.2

Gas Supply

3.2.1

Natural Gas - G20 at 20mbar nominal supply pressure (appliance cat 2H).

Model Max. Supply Pressure

 Min Supply Pressure

Setting Pressure

Gas Connection

Ultra 7

25 mbar

         17 mbar

       19.0 mbar

        Rc - ½

Ultra 14

25 mbar

         17 mbar

       18.8 mbar

        Rc - ½

Ultra 21

25 mbar

         17 mbar

       18.7 mbar

        Rc - ½

Ultra 28

25 mbar

         17 mbar

       18.2 mbar

        Rc - ½

Ultra 42

25 mbar

         17 mbar

       17.5 mbar

        Rc - ½

3.2.1.1  Installation pipes should be fitted in accordance with National and Local Regulations.  Pipes of a smaller size than

the appliance connection (Rc - ½) should not be used and the pipework must be designed to achieve the nominal
gas supply pressure of 20 mbar, measured at the appliance inlet pressure test point.

A union service cock MUST be fitted as close as practicable upstream of the appliance to enable the gas train to be
removed for maintenance or repair.

It is essential to provide a flexible metallic hose, which must conform to National or Local Regulations, to connect the

appliance to the gas supply.  Minimum size to be ½" (12.7mm) bore.

3.2.2

LPG - G31 (Propane) at 50mbar nominal supply pressure (appliance cat 3P).

Model      Max. Supply Pressure     Min Supply Pressure    Setting Pressure     Gas Connection

Ultra 7

57.5 mbar

42.5 mbar

 50.0 mbar

       Rc - ½

Ultra 14

57.5 mbar

    

42.5 mbar

 50.0 mbar

       Rc - ½

Ultra 21

57.5 mbar

    

42.5 mbar

 50.0 mbar

       Rc - ½

Ultra 28

57.5 mbar

    

42.5 mbar

 50.0 mbar

       Rc - ½

Ultra 42

57.5 mbar

          

42.5 mbar

 50.0 mbar

       Rc - ½

Содержание Ultra 14

Страница 1: ...S Ultra 7 Ultra 7 3 5 HI LO Ultra 14 Ultra 14 7 HI LO Ultra 21 Ultra 21 10 5 HI LO Ultra 28 Ultra 28 14 HI LO Ultra 42 Ultra 42 21 HI LO Gas Fired Products UK Ltd Chapel Lane Claydon Ipswich Suffolk I...

Страница 2: ......

Страница 3: ...2 Ultra 7 14 21 28 42 12 4 3 Ultra 7 3 5 14 7 21 10 5 28 14 42 21 12 5 Commissioning 13 14 5 1 Ignition 13 5 2 Shut Down 13 5 3 Checking Gas Pressure 13 14 5 4 Flame Supervision 14 6 Servicing 15 16...

Страница 4: ...Qn 13 33 kW Hs 12 0 kW Hi Appliance Type A1 Appliance Cat I2H I3P Adjusted for 2H G20 20 mbar 3P G31 50 mbar Setting Pressure 18 8 mbar 50 0 mbar Injector 2 x 1 85mm 2 x 1 20mm Orifice Plate 38mm 40m...

Страница 5: ...50Hz 25W Fuse Externally 3A Gas Connection Rc Dimensions L 1 59m W 0 58m H 0 35m Weight 39 Kg Table 5 MODEL Ultra 42 N Ultra 42 L Heat Input Qn 39 96 kW Hs 36 0 kW Hi 37 74 0 kW Hs 34 0kW Hi Appliance...

Страница 6: ...6 0 kW Hi Appliance Type A1 Appliance Cat I2H I3P Adjusted for 2H G20 20 mbar 3P G31 50 mbar Setting Pressure 18 8 mbar 50 0 mbar Injector 2 x 1 85mm 2 x 1 20mm Orifice Plate 38mm 40mm Electrical Sup...

Страница 7: ...use Externally 3A Gas Connection Rc Dimensions L 1 59m W 0 58m H 0 35m Weight 39 Kg Table 10 MODEL Ultra 42 21 HI LO N Ultra 42 21 HI LO L Heat Input Qn 39 96 kW 19 98 kW Hs 37 74 kW 18 87kW Hs 36 00...

Страница 8: ...it is recommended that suitable protected welded chain 3mm x 65 links m or 6mm minimum mild steel drop rods and suitable brackets are used Attach the chains or drop rods to the 4 suspension screws of...

Страница 9: ...itted in accordance with National and Local Regulations Pipes of a smaller size than the appliance connection Rc should not be used and the pipework must be designed to achieve the nominal gas supply...

Страница 10: ...pliance must be installed in accordance with the latest or current National Regulations and any Local Regulations that apply Electrical supply 230v 50Hz 25W Current rating 0 11A Fuse externally 3A 3 3...

Страница 11: ...having a constant separation of at least 3mm in all poles and supplying the appliance ONLY Alternatively connections may be made via a 3 pin plug and unswitched socket both complying with the requirem...

Страница 12: ...ieved by any of the three following different means a thermal evacuation of the products of combustion air mixture b mechanical evacuation of the products of combustion air mixture c natural air chang...

Страница 13: ...the outside atmosphere by a sufficient natural air change in the installation room Furthermore no provision for thermal or mechanical ventilation is required in the following particular cases building...

Страница 14: ...ed fitted to junction box attached to the Control Valve as follows Brown to terminal marked 1 Blue to terminal marked 2 Green Yellow to terminal marked 7 External fuse required 3 amp See section 3 3 f...

Страница 15: ...a first reset is not successful wait at least 15 seconds before repeating the procedure After reset an extended waiting time will occur 5 1 8 If the burner fails to ignite following a second ignition...

Страница 16: ...tra 14 Ultra 14 7 50 0mbar Ultra 21 Ultra 21 10 5 50 0mbar Ultra 28 Ultra 28 14 50 0mbar Ultra 42 Ultra 42 21 50 0mbar 5 3 2 3 In the event that the burner setting pressure is incorrect remove the cap...

Страница 17: ...mm If the electrode is badly oxidised or the ceramic insulator is cracked replace the electrode assembly see section 7 1 6 1 5 Remove any foreign matter from the flame sensor rod and check the conditi...

Страница 18: ...ition control 7 2 2 Remove the screw securing the ignition control to the Honeywell gas control valve and remove the connection cover 7 2 3 Disconnect the 10 way Molex electrical connector from the ig...

Страница 19: ...embly ceramic tiles 7 6 1 In the unlikely event that a ceramic tile is damaged and requires replacement contact Space Ray at the address shown on the front cover of this manual 7 7 Replacement Parts L...

Страница 20: ...Gas Supply to the appliance Gas Setting pressure in accordance with section 3 2 of manual YES Is Ignition spark present at Electrodes YES Does Ignition Spark cease when Burner ignites NO NO NO Adjust...

Страница 21: ...NOTES Page 19 of 20...

Страница 22: ...Page 20 of 20 09 03 GB IE 525S...

Отзывы: