COMMISSIONING

It is essential that all new pipework installations are purged and tested for soundness using a suitable leak detection
fluid prior to attempting to ignite any appliance.  This work should be carried out in accordance with National or Local
Regulations.

N.B.  DO NOT TEST FOR SOUNDNESS BY USE OF NAKED FLAMES

.

5.1

Ignition

.

5.1.1 

Turn on the gas supply to the appliance.

5.1.2 

Switch on the electrical supply to the appliance.

5.1.3 

If the appliance has a thermostat fitted in the electrical supply circuit, ensure that it is set high enough to demand
heat.  Ultra HI/LO (e.g. Ultra 7/3.5): ensure that the second thermostat (T2 - see Fig. 4) is set high enough to call for
heat also.

5.1.4 

After a waiting time of 1 second, the solenoid valves and the spark ignition electrode will be energised
simultaneously.

5.1.5 

Upon successful ignition the flame will be detected by the flame sensor and the ignition spark electrode will be de-
energised.

5.1.6 

Should the flame fail to permanently establish during the 25 seconds ignition period, the solenoid valves and ignition
spark electrode will be de-energised and the appliance Ignition Control will go to "lockout" condition.

5.1.7 

To repeat the ignition sequence it will be necessary to switch off the electricity supply to the appliance for a period of
10 seconds to reset the ignition control.  If a first reset is not successful, wait at least 15 seconds before repeating
the procedure.  After reset, an extended waiting time will occur.

5.1.8 

If the burner fails to ignite following a second ignition sequence, turn off the gas supply at the gas isolation valve and
investigate the fault.

5.1.9 

If gas failure occurs after successful ignition the appliance ignition control will attempt one re-ignition before going to
"lockout" condition.

5.1.10  Ultra HI/LO (e.g. Ultra 7/3.5) only:  with the burner ignited, turn down the temperature setting of the second

thermostat (T2-see Fig. 4) and observe that the tile colour changes from bright cherry red to dull red.  (Low burn
condition - LO - heat input reduced to 50%).  To increase the heat input to 100% (HI), turn up the temperature
setting of the second thermostat (T2).

IMPORTANT:  Thermostat T1 must be set at a higher temperature than thermostat T2 to achieve the High/Low
mode of operation.

5.2

Shut Down

5.2.1 

To shut down the appliance for short periods of time, switch off the electrical supply to the appliance.

5.2.2 

To shut down the appliance for a period of time in excess of one week, switch off the electrical supply to the
appliance and turn off the gas supply at the gas isolation valve.

Note:  concise operating instructions are contained on Instruction Label (4260460) that should be affixed adjacent to
a low level user control.

5.3

Checking Gas Pressure

5.3.1 

To check the gas supply pressure.

5.3.1.1  Unscrew the sealing screw (2 turns) of the control valve test nipple marked 'IN' and connect a manometer to this test

nipple.

Содержание Ultra 14

Страница 1: ...S Ultra 7 Ultra 7 3 5 HI LO Ultra 14 Ultra 14 7 HI LO Ultra 21 Ultra 21 10 5 HI LO Ultra 28 Ultra 28 14 HI LO Ultra 42 Ultra 42 21 HI LO Gas Fired Products UK Ltd Chapel Lane Claydon Ipswich Suffolk I...

Страница 2: ......

Страница 3: ...2 Ultra 7 14 21 28 42 12 4 3 Ultra 7 3 5 14 7 21 10 5 28 14 42 21 12 5 Commissioning 13 14 5 1 Ignition 13 5 2 Shut Down 13 5 3 Checking Gas Pressure 13 14 5 4 Flame Supervision 14 6 Servicing 15 16...

Страница 4: ...Qn 13 33 kW Hs 12 0 kW Hi Appliance Type A1 Appliance Cat I2H I3P Adjusted for 2H G20 20 mbar 3P G31 50 mbar Setting Pressure 18 8 mbar 50 0 mbar Injector 2 x 1 85mm 2 x 1 20mm Orifice Plate 38mm 40m...

Страница 5: ...50Hz 25W Fuse Externally 3A Gas Connection Rc Dimensions L 1 59m W 0 58m H 0 35m Weight 39 Kg Table 5 MODEL Ultra 42 N Ultra 42 L Heat Input Qn 39 96 kW Hs 36 0 kW Hi 37 74 0 kW Hs 34 0kW Hi Appliance...

Страница 6: ...6 0 kW Hi Appliance Type A1 Appliance Cat I2H I3P Adjusted for 2H G20 20 mbar 3P G31 50 mbar Setting Pressure 18 8 mbar 50 0 mbar Injector 2 x 1 85mm 2 x 1 20mm Orifice Plate 38mm 40mm Electrical Sup...

Страница 7: ...use Externally 3A Gas Connection Rc Dimensions L 1 59m W 0 58m H 0 35m Weight 39 Kg Table 10 MODEL Ultra 42 21 HI LO N Ultra 42 21 HI LO L Heat Input Qn 39 96 kW 19 98 kW Hs 37 74 kW 18 87kW Hs 36 00...

Страница 8: ...it is recommended that suitable protected welded chain 3mm x 65 links m or 6mm minimum mild steel drop rods and suitable brackets are used Attach the chains or drop rods to the 4 suspension screws of...

Страница 9: ...itted in accordance with National and Local Regulations Pipes of a smaller size than the appliance connection Rc should not be used and the pipework must be designed to achieve the nominal gas supply...

Страница 10: ...pliance must be installed in accordance with the latest or current National Regulations and any Local Regulations that apply Electrical supply 230v 50Hz 25W Current rating 0 11A Fuse externally 3A 3 3...

Страница 11: ...having a constant separation of at least 3mm in all poles and supplying the appliance ONLY Alternatively connections may be made via a 3 pin plug and unswitched socket both complying with the requirem...

Страница 12: ...ieved by any of the three following different means a thermal evacuation of the products of combustion air mixture b mechanical evacuation of the products of combustion air mixture c natural air chang...

Страница 13: ...the outside atmosphere by a sufficient natural air change in the installation room Furthermore no provision for thermal or mechanical ventilation is required in the following particular cases building...

Страница 14: ...ed fitted to junction box attached to the Control Valve as follows Brown to terminal marked 1 Blue to terminal marked 2 Green Yellow to terminal marked 7 External fuse required 3 amp See section 3 3 f...

Страница 15: ...a first reset is not successful wait at least 15 seconds before repeating the procedure After reset an extended waiting time will occur 5 1 8 If the burner fails to ignite following a second ignition...

Страница 16: ...tra 14 Ultra 14 7 50 0mbar Ultra 21 Ultra 21 10 5 50 0mbar Ultra 28 Ultra 28 14 50 0mbar Ultra 42 Ultra 42 21 50 0mbar 5 3 2 3 In the event that the burner setting pressure is incorrect remove the cap...

Страница 17: ...mm If the electrode is badly oxidised or the ceramic insulator is cracked replace the electrode assembly see section 7 1 6 1 5 Remove any foreign matter from the flame sensor rod and check the conditi...

Страница 18: ...ition control 7 2 2 Remove the screw securing the ignition control to the Honeywell gas control valve and remove the connection cover 7 2 3 Disconnect the 10 way Molex electrical connector from the ig...

Страница 19: ...embly ceramic tiles 7 6 1 In the unlikely event that a ceramic tile is damaged and requires replacement contact Space Ray at the address shown on the front cover of this manual 7 7 Replacement Parts L...

Страница 20: ...Gas Supply to the appliance Gas Setting pressure in accordance with section 3 2 of manual YES Is Ignition spark present at Electrodes YES Does Ignition Spark cease when Burner ignites NO NO NO Adjust...

Страница 21: ...NOTES Page 19 of 20...

Страница 22: ...Page 20 of 20 09 03 GB IE 525S...

Отзывы: