Space-Ray Ultra 14 Скачать руководство пользователя страница 2

Содержание Ultra 14

Страница 1: ...S Ultra 7 Ultra 7 3 5 HI LO Ultra 14 Ultra 14 7 HI LO Ultra 21 Ultra 21 10 5 HI LO Ultra 28 Ultra 28 14 HI LO Ultra 42 Ultra 42 21 HI LO Gas Fired Products UK Ltd Chapel Lane Claydon Ipswich Suffolk I...

Страница 2: ......

Страница 3: ...2 Ultra 7 14 21 28 42 12 4 3 Ultra 7 3 5 14 7 21 10 5 28 14 42 21 12 5 Commissioning 13 14 5 1 Ignition 13 5 2 Shut Down 13 5 3 Checking Gas Pressure 13 14 5 4 Flame Supervision 14 6 Servicing 15 16...

Страница 4: ...Qn 13 33 kW Hs 12 0 kW Hi Appliance Type A1 Appliance Cat I2H I3P Adjusted for 2H G20 20 mbar 3P G31 50 mbar Setting Pressure 18 8 mbar 50 0 mbar Injector 2 x 1 85mm 2 x 1 20mm Orifice Plate 38mm 40m...

Страница 5: ...50Hz 25W Fuse Externally 3A Gas Connection Rc Dimensions L 1 59m W 0 58m H 0 35m Weight 39 Kg Table 5 MODEL Ultra 42 N Ultra 42 L Heat Input Qn 39 96 kW Hs 36 0 kW Hi 37 74 0 kW Hs 34 0kW Hi Appliance...

Страница 6: ...6 0 kW Hi Appliance Type A1 Appliance Cat I2H I3P Adjusted for 2H G20 20 mbar 3P G31 50 mbar Setting Pressure 18 8 mbar 50 0 mbar Injector 2 x 1 85mm 2 x 1 20mm Orifice Plate 38mm 40mm Electrical Sup...

Страница 7: ...use Externally 3A Gas Connection Rc Dimensions L 1 59m W 0 58m H 0 35m Weight 39 Kg Table 10 MODEL Ultra 42 21 HI LO N Ultra 42 21 HI LO L Heat Input Qn 39 96 kW 19 98 kW Hs 37 74 kW 18 87kW Hs 36 00...

Страница 8: ...it is recommended that suitable protected welded chain 3mm x 65 links m or 6mm minimum mild steel drop rods and suitable brackets are used Attach the chains or drop rods to the 4 suspension screws of...

Страница 9: ...itted in accordance with National and Local Regulations Pipes of a smaller size than the appliance connection Rc should not be used and the pipework must be designed to achieve the nominal gas supply...

Страница 10: ...pliance must be installed in accordance with the latest or current National Regulations and any Local Regulations that apply Electrical supply 230v 50Hz 25W Current rating 0 11A Fuse externally 3A 3 3...

Страница 11: ...having a constant separation of at least 3mm in all poles and supplying the appliance ONLY Alternatively connections may be made via a 3 pin plug and unswitched socket both complying with the requirem...

Страница 12: ...ieved by any of the three following different means a thermal evacuation of the products of combustion air mixture b mechanical evacuation of the products of combustion air mixture c natural air chang...

Страница 13: ...the outside atmosphere by a sufficient natural air change in the installation room Furthermore no provision for thermal or mechanical ventilation is required in the following particular cases building...

Страница 14: ...ed fitted to junction box attached to the Control Valve as follows Brown to terminal marked 1 Blue to terminal marked 2 Green Yellow to terminal marked 7 External fuse required 3 amp See section 3 3 f...

Страница 15: ...a first reset is not successful wait at least 15 seconds before repeating the procedure After reset an extended waiting time will occur 5 1 8 If the burner fails to ignite following a second ignition...

Страница 16: ...tra 14 Ultra 14 7 50 0mbar Ultra 21 Ultra 21 10 5 50 0mbar Ultra 28 Ultra 28 14 50 0mbar Ultra 42 Ultra 42 21 50 0mbar 5 3 2 3 In the event that the burner setting pressure is incorrect remove the cap...

Страница 17: ...mm If the electrode is badly oxidised or the ceramic insulator is cracked replace the electrode assembly see section 7 1 6 1 5 Remove any foreign matter from the flame sensor rod and check the conditi...

Страница 18: ...ition control 7 2 2 Remove the screw securing the ignition control to the Honeywell gas control valve and remove the connection cover 7 2 3 Disconnect the 10 way Molex electrical connector from the ig...

Страница 19: ...embly ceramic tiles 7 6 1 In the unlikely event that a ceramic tile is damaged and requires replacement contact Space Ray at the address shown on the front cover of this manual 7 7 Replacement Parts L...

Страница 20: ...Gas Supply to the appliance Gas Setting pressure in accordance with section 3 2 of manual YES Is Ignition spark present at Electrodes YES Does Ignition Spark cease when Burner ignites NO NO NO Adjust...

Страница 21: ...NOTES Page 19 of 20...

Страница 22: ...Page 20 of 20 09 03 GB IE 525S...