
Form 43539178
Oct 2019
13
TABLE 1
. -- LP
Gas Pipe Sizing between Single or Second Stage Regulator and Brooders.
Tubing Size, O.D. Type L
Nominal Pipe Size, I.D. Schedule 40
3/8”
1/2”
5/8”
3/4”
7/8”
1-1/8”
1/2”
3/4”
1”
1-1/4”
1-1/2”
2”
3”
4”
3m
11.4
27
58.3
96.4
147
274
85.3
178
336
690
1030
1990
5610
11400
6m
7.62
18.2
38.4
63.3
101
185
58.6
123
231
474
710
1370
3850
7860
9m
6.15
14.7
31.4
53
81.2
147
47.2
98.5
185
381
570
1100
3090
6310
12.5m
5.57
12
26.4
42.5
68.3
125
40.2
84.1
159
326
488
940
2650
5400
15m
5.28
10.8
23.2
38.4
58
110
35.8
74.7
141
289
433
833
2350
4790
18.5m
4.69
10.3
21.1
35.5
54.8
99.6
32.2
67.7
127
261
392
755
2130
4340
24.5m
3.81
8.5
18.2
30.5
45.4
84.7
27.5
58
109
224
335
646
1820
3710
31m
3.22
7.62
16.1
26.4
40.4
74.7
24.6
51.3
96.7
198
297
573
1610
3290
38.5m
2.93
7.03
14.1
23.7
35.8
65.6
21.7
45.4
85.6
176
263
507
1430
2920
46m
2.64
6.15
12.6
21.1
31.9
59.2
19.6
41.3
77.7
159
239
460
1300
2640
61.5m
2.34
5.57
11.4
19.3
29.3
54.8
17
35.2
66.5
136
204
394
1110
2260
77m
2.34
4.98
10.6
17.6
27.3
50.4
14.9
31.4
58.9
121
181
349
983
2000
92m
---
---
---
---
---
---
13.5
28.4
53.3
110
164
316
890
1820
107.5m
---
---
---
---
---
---
12.6
26.1
48.9
101
151
291
819
1670
123m
---
---
---
---
---
---
11.7
24.3
45.7
93.8
140
271
762
1550
Maximum propane capacities listed are based on 1.25mbar pressure drop at 30mbar setting - Capacities in kW.
TABLE 2.
Brooder #
Distance from
Regulator m
Flow Capacity
Required kW
Distance Used from
Table m (ft.)
Smallest Pipe Size and
Capacity From Table kW
(Btu/hr)
7 and 14
62
11.7
61.5
½”
--
17
6 and 13
53.5
23.4
61.5
¾”
--
35.2
5 and 12
45
35.2
46
¾”
--
41.3
4 and 11
36
46.9
38.5
1”
--
85.6
3 and 10
27.5
58.6
31
1”
--
96.7
2 and 9
19
70.3
18.5
Note 1
1”
--
127
1 and 8
10.5
82.1
12.5
1”
--
159
Note 2
Note 1: The distance used is rounded down to 18.5 (60).
Note 2: The actual smallest pipe size for the required capacity is ¾” from the table. However, the gas pipe size from
brooders 3 and 4 to the regulator must be 1” diameter and therefore a smaller diameter pipe cannot be used. If ¾” pipe
was used from the Tee to brooder 1, the pressure drop in the rest of the system would exceed the design pressure drop of
1.25mbar.
8.
ELECTRICAL CONNECTIONS – No. 2 and No. 4 Control
1. All electrical wiring to this brooder must be installed in accordance with the latest or current
National Regulations and any Local Regulations, which apply.
2. The electrical system must be electrically grounded in accordance with the latest or current
National Regulations and any Local Regulations, which apply.
3. The brooders with the #9 control options do not require any electrical supply because they
generate their own electricity and operate thermostatically off this power. The brooders with
the #2 control option require a 24VAC supply to each brooder. This is provided via a 24Volt
Transformer. The 24Volt Transformer MUST be large enough to operate the number of
brooders connected to it (see table below). This is calculated as follows: