– 3 –
P/N SCM2-0111
Model
SCM
Air to Water Heat Pump — Installation, Operation & Maintenance Manual
Figure 1
Model SCM rating data
Item
Units
SCM-036
SCM-060
Item
Units
SCM-036
SCM-060
Cooling capacity
(Note 2)
Btuh / KW
34,000 / 10.0
46,000 / 13.5
Supply voltage
VAC
230/1/60
230/1/60
Heating capacity
(Note 3)
Btuh / KW
44,000 / 13.0
60,000 / 17.0
Running current,
cooling
(Note 1)
Amps
17.6
26.4
Fan speed
RPM
850
850
Running current,
heating
(Note 1)
Amps
13.1
21.3
Noise level
dB(A)
56
56
MCA
(Note 1)
Amps
19.7
30.3
Water volume
Gallons
2
2.5
Supply connection
Inches NPT
1
1
Return connection
Inches NPT
1
1
Minimum supply
temperature
°F
36
36
Maximum supply
temperature
°F
125
125
Minimum flow
GPM
7
10
Maximum flow
GPM
12
15
Pressure drop at
minimum flow
Feet WC
8
17
Pressure drop at
maximum flow
Feet WC
21
28
Net weight
Lbs
337
386
Operating weight
Lbs
354
407
Shipping weight
Lbs
346
395
Shipping dimensions
Inches
47 x 18 x 60 47 x 18 x 60
Note 1:
Note 2:
Note 3:
Electrical ratings DO NOT include water pump amp draw. This pump is supplied by the installer. Add the current draw of the pump to
the values listed above. Adjust the MCA accordingly.
Performance at 95° ambient temperature, 45° water
Performance at 47° ambient temperature, 115° water
Figure 2
Model SCM coding
Typical model
S
C
M
0
6
0
A
4
Position
1
2
3
4
5
6
7
8
Designation
Unit Type
Capacity
Series
Refrigerant
type
Values
SCM
= SpacePak Heat Pump/Chiller Module
036
=
3 ton nominal
060
=
5 ton nominal
A
= Series “A”
4
= R410A
Examples
SCM-036-A-4
= 3 ton nominal, series A, using R410A referigerant, SpacePak Heat Pump/Chiller Module
SCM-060-A-4
= 5 ton nominal, series A, using R410A referigerant, SpacePak Heat Pump/Chiller Module
Standard equipment
• Heat pump/chiller, including two refrigeration systems, fac-
tory-programmed controller, fans and all required internal
components
• Powder-coated enclosure
optional equipment
• Auxiliary electric immersion heater (3 KW, 230V/1/60) — re-
quires separate electrical power circuit, 15-amp minimum
breaker
Additional components required
• Pump and piping by others
• Zone valves (must be 3-way, NOT 2-way) or zone pumps for
multi-zone
• Expansion tank (10 gallon minimum)
• SpacePak Chiller Interface Module
Section 2: Specifications and ratings