maintenance on the coils (transformers, engines and motors, generators, 
etc.). 
 

 

 

3.8. Polarization index (PI) 

The   key makes it possible to visualize the Polarization Index  value on 
the  display.  For  this  type  of  test,  the  equipment  must  be  connected  and 
applying  voltage  to  the  sample  for  10  minutes.  After  this  period,  the 
operator  must  press  the 

  key  to  show  the  PI  value  on  the  instrument 

display.  If  the  key  is  pressed  before  the  10-min  period  has  elapsed,  the 
display will show PI= - - -. The polarization index is the ratio between the 
insulation  resistance  value  measured  after  10  min  and  the  value 
measured  after  1  min.  This  index  is  useful  to  determine  whether  it  is 
necessary  to  perform  preventive  and  predictive  Maintenance  in  order  to 
detect any insulation resistance wear and tear due to the excess of dust, 
dirt, grease, or else the action of chemical or physical agents, etc. 
 

 

 
 

3.9. Step Voltage Test (SVT) 

After selecting the SVT function with the   key, the operator must select 
the test maximum voltage with the   key. In this function, the equipment 
allows the selection of maximum voltages only from 500 V up to 5000 V in 
500 V steps. If the operator selects a halfway voltage between two 500 V 
steps  by  using  the    key,  the  equipment  will  carry  out  the  test  from  the 
500 V  up  to  reaching  an  equal  voltage  value  or  a  value  that  is  straight 
below  the  500  multiple  value.  During  the  first  minute  the  generated  test 
voltage  is  of  500 V.  This  voltage  is  incremented  in  500 V  steps  until  it 
reaches the maximum programmed voltage. Each voltage step is applied 
during one minute, and the resistance is measured before going up to the 
following voltage. The test result is calculated with this formula: 

Содержание MD-5060 Series

Страница 1: ...3 MD 5060x 5 kV digital insulation tester User s Guide GU 1290 2008 SOURCETRONIC All rights reserved Printed in Germany...

Страница 2: ...urn off Be careful not to make short circuit between the high voltage terminals and the R or Guard terminals while a measurement is running because it could be dangerous for the operator Be sure that...

Страница 3: ...tmeter 15 3 5 Memory HOLD 15 3 6 Filter 15 3 7 Dielectric Absorption Index DAI 15 3 8 Polarization index PI 16 3 9 Step Voltage Test SVT 16 3 10 Built in printer 17 3 11 Battery status check 17 3 12 A...

Страница 4: ...bling tests recording NVRAM memory enabling storing up to 4000 readings to be later downloaded to an IT equipment Built in chronometer indicating elapsed time in minutes and seconds since the test sta...

Страница 5: ...ance this equipment is suitable for fieldwork under extreme weather conditions It is easy to carry very simple to be operated and resistant to violent treatment which unavoidably includes frequent bum...

Страница 6: ...8 2 Control panel Voltage output terminal V Zero reference terminal R Guard terminal G Display Keyboard RS232 communication port Power supply input Paper feed control...

Страница 7: ...oltage in steps of 500 V It enables the fast voltage selection keys 500 V steps test voltage Fast selection of 500 V test voltage 500 V test voltage Fast selection of 1 kV test voltage 1 kV test volta...

Страница 8: ...tage applied It shows the battery charge status on the display Indicates that the battery charger is in operation Hold freeze the last reading on the display MEM function is on It displays the calcula...

Страница 9: ...measurement result the corresponding measuring unit the elapsed time since the measurement started the analogue indication by means of a bargraph and messages to the operator are displayed in English...

Страница 10: ...n The MD 5060x is an extremely versatile equipment which allows to carry out several kinds of insulation tests automatically recording all the results in its internal memory or printing them It is nec...

Страница 11: ...ge Selects 2 5 kV voltage Selects 5 kV voltage To operate them it is necessary that one of the keys or is selected Increase Decrease test voltage Increases the present test voltage in 500 V or 100 V s...

Страница 12: ...the selected value without any possibility of adjusting it When the selected mode is different from the Normal mode the key led flashes in order to warn the operator that the equipment is programmed f...

Страница 13: ...table especially for resistance values higher than 300 M In these cases it is convenient to press the key before starting the measurement This function allows to reach the insulation resistance value...

Страница 14: ...insulation resistance wear and tear due to the excess of dust dirt grease or else the action of chemical or physical agents etc 3 9 Step Voltage Test SVT After selecting the SVT function with the key...

Страница 15: ...e test in order to print it complete including the heading 3 11 Battery status check During the measurement it is possible to check the battery status The key must be pressed If the battery charge is...

Страница 16: ...during the charging process In order to charge the battery follow this procedure Verify that the On Off switch is switched off Connect the power supply cable plug into input After a while the battery...

Страница 17: ...maged if remains in deep discharge for a while To avoid this effect charge the battery before left the equipment in storage and don t let pass more than 30 days without recharge even if the instrument...

Страница 18: ...e unstable readings When insulation is measured regarding grounding the R terminal is connected to earth and the condition by means of which the equipment potential setting is fulfilled If the measure...

Страница 19: ...ted for the last performed test meanwhile the equipment will be in the 500 V steps voltage test programming mode key led flashing To modify this voltage use the and keys or the fast selection keys For...

Страница 20: ...display will show the test number the selected voltage value and it will start the elapsed time count If the measured value is within the device scope the test number indication will provide place fo...

Страница 21: ...ith Windows operative system easier It makes it possible to synchronize the date and time of the equipment internal clock with the computer date and clock to transfer the stored date to clear the memo...

Страница 22: ...r data to a computer To transfer data from the MD 5060x to a PC type computer use the cable provided with the accessories Connect it to RS232 PORT and the opposite end of your PC RS232 connector Open...

Страница 23: ...ndow In this example the port would be Com 1 After clicking on OK go to the next window to fill out the relevant data 4800 8 none 1 none Now the PC is ready to collect the information obtained from me...

Страница 24: ...26 8 Printer Printing sample...

Страница 25: ...re shown below indicates how to put the paper Press the key until the paper appears To remove the old paper reel cut the paper next to it and press the key The removal used reel operation must be carr...

Страница 26: ...er Prints elapsed time actual voltage applied to the charge and measured resistance Serial data output RS232 4800 bps It allows the connection to a serial printer to a portable computer or a laptop or...

Страница 27: ...e range 25 C to 65 C Humidity range 95 RH non condensing Dimensions 274 x 250 x 124 mm Equipment weight Approx 3 6 kg Supplied accessories 2 Measuring test leads 1 8 m 1 Guard test lead 1 8 m 1 Power...

Страница 28: ...tion of this terminal let us start reviewing the megohmmeter basic circuit diagram of fig 1 Where V DC high voltage generator Ri Generator internal resistance A Indicator meter micro ammeter The unkno...

Страница 29: ...nsulation resistance between primary winding and housing R2 Insulation resistance between secondary winding and housing If megohmmeter terminals Vt and R is connected to transformer terminals A and B...

Страница 30: ...ough R2 originates a certain error since it creates an additional voltage drop in R1 which was not regarded during megohmmeter calibration As regards the practical use of megohmmeter it shall be consi...

Страница 31: ...was caused by misuse alteration accident or abnormal condition or handling you will be charged for the repair and the repaired equipment will be returned to you transportation prepaid This warranty is...

Страница 32: ...34 NOTES...

Отзывы: