Chapter 5 Function parameter
52
Code
Parameter name
Setting range
Factory
default Change
Analog AI2 setting
2
Multi-speed setting
3
Remote communications
setting
4
To define the setting mode for upper limit. The upper limit frequency can be set from
either digital setting (F0.10), also from analog input channels, multi-speed setting or
communication settings. When the analog input setting, multi-speed setting or
communication setting is set to upper limit frequency, the analog input setting 100%
corresponds to F0.08 (maximum output frequency) .
F0.10 Running frequency
upper limit
F0.11 to F0.08 (maximum
output frequency)
50.00Hz
☆
Running frequency upper limit is the upper limit of the inverter output frequency. The
value should be less than or equal to the maximum output frequency.
F0.11 Running frequency
lower limit
0.00Hz to F0.10 (running
frequency upper limit)
0.00Hz
☆
Running frequency lower limit is the lower limit of the inverter output frequency.
When the set frequency is less than the frequency lower limit, the frequency lower
limit will be adopted for running.
Note: maximum output frequency ≥ frequency upper limit ≥
frequency lower limit.
F0.12 Running direction
selection
0: default
1: opposite
2: reverse prohibited
0
★
0: default After the inverter is powered on, it runs at the actual direction.
1: opposite Used to change the motor rotation, which acts to change the motor
direction of rotation by adjusting any two motor wires.
2: reverse prohibited Used to prohibit reverse running of the inverter for the specific
occasions.
Note: after the parameter is initialized, the motor running direction will be restored to
its original status. When the system debugging is completed, please use with caution
where the change of motor steering is strictly prohibited
F0.13 AVR function selection
Invalid
0
1
☆
Full valid
1
Only invalid during
deceleration
2
AVR function that automatically adjusts the output voltage function. When AVR
function is disabled, the output voltage will vary with the change of the input voltage
(or DC bus voltage) ; when AVR function is enabled, the output voltage will not vary
with the change of the input voltage (or DC bus voltage), the output voltage remains
substantially constant within the range of output capacity.