Chapter 5 Function parameter
32
No. Code Parameter name
Setting range
Factory
default Change
Reference
page
85.
F4.09
V/F slip
compensation
limit
0.0 to 200.0%
0.0%
☆
64
5-1-7.F5 Group - Vector control group
No. Code Parameter name
Setting range
Factory
default Change
Reference
page
86.
F5.00 Speed loop
proportional gain 1 0 to 100
20
☆
64
87.
F5.01 Speed loop integral
time 1
0.01 to 10.00s
0.50 s
☆
64
88.
F5.02 Switching low
point frequency
0.00Hz to F5.05
5.00Hz
☆
64
89.
F5.03 Speed loop
proportional gain 2 0 to 100
15
☆
64
90.
F5.04 Speed loop integral
time 2
0.01 to 10.00s
1.00
☆
64
91.
F5.05 Switching high
point frequency
F5.02 to F0.08
(maximum output
frequency)
10.00Hz
☆
64
92.
F5.06
VC slip
compensation
coefficient
50 to 200.0% (rated
inverter current)
100%
☆
65
93.
F5.07 Torque upper limit
setting
0.0 to 200%
150%
☆
65
5-1-8.F6 Group - Keyboard and display
No. Code
Parameters
Setting range
Factory
default Change
Reference
page
94.
F6.00
STOP/RST key
stop function
selection
0: only active to panel
control
1: Valid for both panel
control and terminal
control
2: Valid for both panel
control and
communication control
3: Valid for all control
modes
0
☆
65
Содержание 60961