![Sourcetronic 60961 Скачать руководство пользователя страница 33](http://html1.mh-extra.com/html/sourcetronic/60961/60961_user-manual_1336349033.webp)
Chapter 5 Function parameter
27
No. Code Parameter name
Setting range
Factory
default Change
Reference
page
34.
F0.13 AVR function
selection
0: Invalid
1: full valid
2: only invalid during
deceleration
1
☆
52
5-1-3.F1 Group - Input terminals
No. Code Parameter name
Setting range
Factory
default Change
Reference
page
35.
F1.00 DI1 terminal
function selection
0: No function
1: Forward run
2: Reverse run
3: Three-wire
operation control
4: Forward Jog
5: Reverse Jog
6: Frequency setting
increment (UP)
7: Frequency setting
decrement (DOWN)
8: Free stop
9: Fault reset
10: External fault
input
11: Frequency change
settings clear
12: Multi-speed
terminal 1
13: Multi-speed
terminal 2
14: Multi-speed
terminal 3
15: Multi-speed
terminal 4
16: Ac/deceleration
time selection
17: Control command
switch terminal
18: Ac/deceleration
prohibited
19: STD control
pause
20: Wobbulate pause
(stops at the current
frequency)
1
★
53
36.
F1.01 DI2 terminal
function selection
2
★
53
37.
F1.02 DI3 terminal
function selection
8
★
53
38.
F1.03 DI4 terminal
function selection
9
★
53
39.
F1.04 DI5 terminal
function selection
4
★
53
40.
F1.05 Reserved
Содержание 60961
Страница 6: ......
Страница 21: ...Chapter 2 Standard Specifications 15 2 3 2 Keyboard size diagram JP130 size diagram...