38
Special functions
Deviations in the temperature values displayed, for example due to cables which are to
long or sensors which are not positioned optimally, can be compensated for manually
here. The settings can be made for each individual sensor in steps of 0.8 °C (tempera-
ture) resp. 0.2 % of the measuring range of the VFS / RPS sensor (fl ow rate / pressure)
per step.
Caution
Settings are only necessary in special cases at the time of initial com-
missioning by the specialist. Incorrect measurement values can lead to
unpredictable errors.
All of the settings that have been made can be reset, thus returning the controller to its delivery
state.
Caution
The entire parametrisation, analyses, etc. of the controller will be lost
irrevocably. The controller must then be commissioned once again.
6.7. - Sensor calibration
With some solar systems, especially with vacuum tube collectors, it may occur that the
measurement value acquisition at the collector sensor occurs too slowly or too inac-
curately because the sensor is often not at the hottest location. When the start help is
activated the following sequence is carried out: If the temperature at the collector sen-
sor increases by the value specifi ed under “Increase” within one minute, then the solar
pump is switched on for the set “Purging time” so that the medium to be measured
can be moved to the collector sensor. If this still does not result in a normal switch-on
condition, then the start help function is subject to a 5-minute lockout time.
Caution
This function should only be activated by a specialist if problems arise with
acquisition of measurement values. In particular follow the instructions from
the collector manufacturer.
Starting the commissioning help guides you in the correct order through the basic set-
tings necessary for commissioning, and provides brief descriptions of each parameter
in the display. Pressing the “esc” key takes you back to the previous value so you can
look at the selected setting again or adjust it if desired. Pressing the “esc” more than
once takes you back to the selection mode, thus cancelling the commissioning help.
(see also E.2).
Caution
May only be started by a specialist during commissioning! Observe the
explanations for the the individual parameters in these instructions, and
check whether further settings are necessary for your application.
6.10. - Start aid function
6.9. - Factory settings
6.8. - Commissioning