24
Special functions
All of the settings that have been made can be reset, thus returning the controller to its delivery
state.
6.4 Factory settings
Caution
The entire parametrisation, analyses, etc. of the controller will be lost
irrevocably. The controller must then be commissioned once again.
6.5.1
Turn time
The time in seconds the mixer is switched on (opening or closing), before a new measurement
for the regulation of the
fl
ow temperature is performed.
Settings range: 0.1 sec. to 3 sec. / Default: 2 sec.
6.5.2 Pause factor
Set a value to multiply the calculated pause time with. e.g. a value of 1 would use the
calculated pause time, 0.5 would half the pause time, and 4 quadruple the calculated pause
time.
Settings range: 0.1 to 4.0 / Default: 3.0
6.5.3 Increase
If a fast increase of temperature occurs, this value is added to the
fl
ow temperature, so that
the mixer reacts faster. Once the temperature rises no faster, the measured temperature is
used again. Temperature is measured once every minute.
Settings range: 0 to 20 / Default: 0
6.5 Mixer
Caution
Settings are only to be made during the installation by a specialist. Incorrect
settings may cause severe malfunctions.