20
Settings
5.5. - Tset S3
Thermostat function at sensor 3
If the temperature at sensor 3 exceeds this value (+hysteresis) the corresponding relay
is switched off. If the temperature at sensor 3 falls below this value and the other con-
ditions are also met, the corresponding relay is switched on.
Setting range: from 0°C to 99°C/ Default: 50°C
5.6. - Thermostat periods
Thermostat activity times
Set the desired periods of time when the thermostat should be active. 2 periods can
be set per day, settings can also be copied to other days. Outside the set times the
thermostat is switched off.
Setting range: from 00:00 to 23:59 / Default: 06:00 to 22:00
5.7. - Hysteresis
Hysteresis for thermostat function
By setting the hysteresis value the heating of the storage tank can be adjusted.If the
temperature of the Tsetpoint at sensor is exceeded by the set hysteresis, additional
heating is deactivated.
Setting range: from 0°C to 20°C / Default: 10°C
Temperature of the water fed into the system
The temperature of the water for domestic use fed into the system can be set here.
This is used to calculate the heat amount.
Settings range: 0°C to 60°C / Default : 10°C
5.8. - Cold water
5.9. - VFS-Type
Select the type of
fl
ow sensor used.
Settings range: 1-12l/min, 1-20l/min, 2-40l/min, 5-100l/min, 10-200l/min, 20-400l/min
5.10. - Comfort
The heat exchanger is rinsed every 15 minutes to keep it warm.
Settings range: On, Off / Default: Off