The flow sensor Superstatic 440 can be operated from 0,5 bar pipe pressure.
To prevent
cavitation
the operating pressure with a flow sensor Superstatic 440
must follow the recommendation in the table below. The Superstatic 440 must
not be exposed to pressures below ambient pressure.
Flow
Static Pressure (bar)
q
% qp
T = 80°C
T = 130°C
qi (qmin)
1
1,0
3,3
qp
100
1,5
4,0
qs
200
3,0
6,0
Flow direction
Horizontal Mounting Position
Horizontal Mounting position
The sensor head MUST be placed to the side +/- 45° in relation to the pipe axis
to avoid influences of air inclusions (top) or dirt (bottom).
Vertical mounting position
Mounting in upward or downward pipes possible.
General notice for mounting:
After mounting and before commissioning purge system > 10 min at qp to avoid
air bubbles.