![background image](http://html1.mh-extra.com/html/sonel/lkg-720/lkg-720_operation-manual_1320061044.webp)
LKZ-720 OPERATING MANUAL version 1.02
42
2
Press and hold until the screen with
settings is displayed.
3
or
select
I
or
Auto
mode.
4
Confirm.
5
or
set the required signal level.
In the circuit, the current signal is forced
with a value equal to the level of:
1 = 10mA
2 = 20mA
3 = 40mA
4 = 80mA (limited working time *)
5 = 160mA (limited working time *)
6
Connect one of the banana sockets of
the transmitter to the one opening of the
wall outlet.
Fig. 27
7
Connect the second banana socket of
the transmitter to the second opening of
the wall outlet.
Fig. 27
8
Start the transmission.
Flashing LED:
green
-
correctly selected mode.
red
–
incorrectly selected mode.
Receiver:
9
Turn the receiver ON.
10
Pressing the button set
FUSE
mode.
11
Move the head of the receiver along the
tested switchboard. When a protection
device is detected, the receiver will
generate a sound signal and activate the
flashlight.
Fig. 27
*
-
transmission level 80mA and 160mA at network voltage of 230V AC cause rapid heating of the
transmitter circuits and its blockade lasting until they cool down.