LKZ-720 OPERATING MANUAL version 1.02
41
5.4 Identifying fuses in a switchboard
LKZ-720 system may be used for identifying safety devices in a circuit. In the analysed circuit a
current signal is forced, for which a protection is searched in the switchboard. The transmitter must
be connected to the circuit in a manner enabling the current flow in the circuit. Connection example
Fig. 27.
Rememberer that cables and busbars in switchboards / distribution boxes may falsify the indica-
tion of the receiver. To make sure whether the detected fuse/circuit breaker is in the tested circuit, re-
move the cover of the switchboard and approach the receiver directly to wires and try to locate the
circuit.
You may also continue the search using a wireless NCP probe (sec 6.4). Hold it in perpendicular
to the switchboard, remembering the arrows on the probe should indicate the top and bottom the
overcurrent circuit breaker.
Fig. 27 Identifying safety devices in a switchboard.
The procedure for setting the system to identify safety devices in the switchboard.
No.
Operation
Screen
Transmitter:
1
Turn the transmitter ON.