![SOMFY Animeo 1870452 Скачать руководство пользователя страница 12](http://html.mh-extra.com/html/somfy/animeo-1870452/animeo-1870452_manual_1317508012.webp)
animeo KNX 4 DC Motor Controller
28.02.2019
WM 24 V DC
2019 Somfy Activités SA
Ref. 5147817A
12/56
5 Communication objects
5.1 Object overview
At the most, 177 communication objects are available for use, but not all at once. A maximum of 250 group
addresses can be connected.
5.1.1 List of Objects
No. Object name
Type
DPT_ID Description
1
Motor 1 Up/Down, Close/Open
1 bit
1.008
If a telegram with the value “0” is received on this
communication object, the appropriate blind goes
up or the window closes. If a telegram with the
value “1” is received, the appropriate blind goes
down or the window opens. At expiration of the
adjusted running time for the UP and DOWN
direction the relays of the outputs are deac-
tivated.
2
Motor 2 Up/Down, Close/Open
1 bit
1.008
3
Motor 3 Up/Down, Close/Open
1 bit
1.008
4
Motor 4 Up/Down, Close/Open
1 bit
1.008
9
Motor 1 Step/Stop
1 bit
1.008
With Venetian blinds: If the Venetian blind is
moving, the move is stopped with the receiving of
a telegram on one of these communication ob-
jects, no matter whether
“0” or “1” is received. If
the Venetian blind is stationary, a turn is carried
out. In addition, the slats turn CLOSED with the
receiving of a telegram with the value
“1” and UP
with the receiving of a telegram with the value
“0”. The duration of the turning step is defined in
the parameter settings.
With vertical awnings, roller shutters, awnings
and windows: When one of the end products is
moving, the move is stopped with the receiving of
a telegram on one of these communication ob-
jects, no matter whether
“0” or “1” is received. If
one of these end products is not moving and a
telegram is received on one of these communica-
tion objects, then no operation is carried out.
10
Motor 2 Step/Stop
1 bit
1.008
11
Motor 3 Step/Stop
1 bit
1.008
12
Motor 4 Step/Stop
1 bit
1.008
13
Motor 1 Position Up/Down
1 Byte 5.001
If a telegram is received on one of these commu-
nication objects, the corresponding blind will
move to the position which is defined by the
received value
“0” = upper/”100” = lower.
With Venetian blinds: When the position is
reached, the same slats angle is moved to at
which the Venetian blind was before.
14
Motor 2 Position Up/Down
1 Byte 5.001
15
Motor 3 Position Up/Down
1 Byte 5.001
16
Motor 4 Position Up/Down
1 Byte 5.001
17
Motor 1 Slat position
1 Byte 5.001
With Venetian blinds: If a telegram is received on
one of these communication objects, the corre-
sponding slats will move to the position which is
defined by the received value. If a Venetian blind
18
Motor 2 Slat position
1 Byte 5.001
19
Motor 3 Slat position
1 Byte 5.001