30 User Manual UM0025_ASW3000-6000H-S2_EN_V02_0722
The higher grid impedance of the AC cable makes it easier to
disconnect from the grid due to excessive voltage at the feed-in
point.
The maximum cable lengths depend on the conductor cross-
section as follows:
Conductor
cross-
section
Maximum cable length
ASW3000
H-S2
ASW3680
H-S2
ASW4000
H-S2
ASW5000
H-S2
ASW6000
H-S2
2.5 mm²
46m
37 m
28 m
17 m
6m
4 mm²
74 m
59 m
44 m
28 m
12m
6 mm²
110 m
89 m
67 m
42 m
20m
The required conductor cross-section depends on the inverter
rating, ambient temperature, routing method, cable type, cable
losses, applicable installation requirements of the country of
installation, etc.
Residual current protection
The product is equipped with an integrated universal current-
sensitive residual current monitoring unit inside. The inverter will
disconnect immediately from the mains power as soon as fault
current with a value exceeding the limit.
If an external residual-current device is required, install a type
B residual-current device which trips at a residual current of
100 mA or higher.