User Manual UM0025_ASW3000-6000H-S2_EN_V02_0722 37
6.6 Second protective grounding connection
If additional grounding or equipotential bonding is required
locally, you can connect additional grounding to the inverter. This
prevents touch current if the grounding conductor on the AC
connector fails.
Procedure:
1. Insert the grounding conductor into the suitable terminal lug
and crimp the contact.
2. Align the terminal lug with the grounding conductor.
3. Insert the screw through the hole located at the housing and
tighten it firmly (screwdriver type: PH2, torque: 1.6Nm).
Risk of injury due to electric shock when you touch the
connector on machine side that don’t be connected a client
connector.
• Make sure the client connector is installed correctly.
• Make sure the client connector also is installed correctly
even you don’t need connect the wire to the EPS port.
Содержание ASW H-S2 Series
Страница 1: ......
Страница 88: ...User Manual UM0025_ASW3000 6000H S2_EN_V02_0722 87...