Sollatek PowerBack PB5000 Скачать руководство пользователя страница 8

the PowerBack PB5000 is able to supply the majority of mains operated domestic and office  
appliances, including small motors, lights, fans, refrigerators and air conditioners up to a maximum 
total demand of 5kVa.

Note: In extreme circumstances where the utility supply remains off and the battery back up has 
expired, appliances such as fridges and air conditioners require approximately 3 minutes restart 
delay (time is required to balance the refrigerant gas) before utility mains is reinstated . Please 
contact Sollatek distributors for advice on the Sollatek Voltshield premium range of products.

Positioning of PowerBack and battery system

the Powerback is designed to operate in a restricted access location, lockable and accessible only 
by competent persons. Installation must be in accordance with the requirements of IeC 60364-4-42. 

the PowerBack must be installed in a dry shaded and dust free location with 300mm spacing all 
round the unit to allow adequate ventilation. the unit has forced cooling and the fans operate full time 
(Saver mode allow fans to turn off when no load applied)

Batteries must be installed in a dry shaded location. take extra care to ensure there is adequate 
ventilation to prevent build up of explosive gases (depending on battery type used).  

Batteries

 

the PowerBack requires a 48V dc battery bank with an absolute minimum capacity of 100ah,  200ah 
is the recommended minimum capacity to provide a realistic backup time (autonomy). Please refer 
to figure 2 for battery set up. Before proceeding, ensure you have appropriate sized batteries for this 
inverter. the unit can use deep cycle flooded lead-acid, or sealed Gel/aGM lead-acid batteries so 
ensure that your batteries are in one of these categories.

-

+

-

+

-

+

-

+

12V

12V

12V

12V

-

INVE R T E R

PB5000

+

-

Figure 2. 48V batteries string wiring (4 x12Vdc)

Battery Cable size

table below shows the minimum recommended battery cable size.

 

Model Number 

Minimum amperage 

1-3 metre one-way 

torque value

PowerBack PB5000 

125 a 

25mm csa. 4awG (min) 

10-15 Nm

 

 

Minimum recommended battery cable size 

8     S o l l at e k   P o w e r B a c k   M a N U a l

       

Содержание PowerBack PB5000

Страница 1: ...PowerBack PB5000 5KVA 220 230Vac 48Vdc INVERTER CHARGER USER MANUAL the power to protec t...

Страница 2: ...Cable Connection 9 AC Cable Size 10 AC Connections 11 AC Isolation and Overcurrent Protection 12 AC Loads 12 Protecting your PowerBack 12 Commissioning of PowerBack 12 OPERATION 13 Front Panel Control...

Страница 3: ...DANGEROUS BATTERIES GENERATE EXPLOSIVE GASES DURING NORMAL OPERATION Provide ventilation to outdoors from the battery compartment The battery enclosure should be designed to prevent accumulation and c...

Страница 4: ...ow a spark or flame in vicinity of a battery or generator 7 Be extra cautious when working with metal tools on and around batteries Potential exists to short circuit the batteries or other electrical...

Страница 5: ...only INSTALLATION Warning Installation must only be carried out by a competent person who has sufficient electrical training and is familiar with safe practices when working on or near electrical sys...

Страница 6: ...B a c k M A N U AL Figure 1 1 Utility Backup B A T T E R Y B A N K L O A D S A C P C T E L E V I S I O N H O M E E L E C T R O N I C S AC DISTRIBUTION PANEL U T I L I T Y S U P P L I E R TO PRIMARY S...

Страница 7: ...ble Energy Source S O L A R H Y D R O W I N D B A T T E R Y B A N K L O A D S A C R E F R I G E R A T I O N O F F I C E F A C T O R Y E L E C T R O N I C S M A I N S O R G E N E R A T O R S T A N D B...

Страница 8: ...t to allow adequate ventilation The unit has forced cooling and the fans operate full time Saver mode allow fans to turn off when no load applied Batteries must be installed in a dry shaded location T...

Страница 9: ...ce the ring terminal of DC cable over the bolt and directly against the unit s battery terminal Tighten the M8 screw to 5 8 Nm Do not place anything between the flat part of the Backup System terminal...

Страница 10: ...n lifting heavy items Caution Do NOT place anything between battery cable ring terminals and terminals on the inverter The terminal screw is not designed to carry current Apply Anti oxidant paste to t...

Страница 11: ...s isolated Turning off the PowerBack does not constitute disconnection from the battery Step 2 Feed the wires through cable clamp and AC cover See Figure 4 Figure 4 AC Cable Connections to unit Step 3...

Страница 12: ...or 40A advised depending on cable type selected installation method and ambient operating temperatures Consult with local regulations AC Loads The AC load or loads must be suitably protected with app...

Страница 13: ...ON Located on front of PowerBack PB5000 To de energise the PowerBack System Turn off PowerBack Switch off mains Open battery isolator fuse Turn on PowerBack for 30 seconds then back off to dissipate a...

Страница 14: ...nfiguration mode there are 4 configuration pages in total Turn page by pressing configuration button Page Description Selectable option 1 Input range Normal generator wide range 2 Output range 220v 23...

Страница 15: ...lays input voltage output voltage and load percentage information Inverter Mode Indicator The inverter mode symbol will appear and the indicator displays input voltage output voltage and load informat...

Страница 16: ...eft ON OFF OFF OFF OFF Low battery alarm flash OFF OFF OFF OFF 1beep 2s Low battery off flash OFF OFF OFF OFF Load indicator Indicates the load percentage in VA or W whichever is the higher the overlo...

Страница 17: ...r cycle will then reset Internal Circuit Breaker The unit contains one 40A input circuit breaker located on the rear panel of the chassis adjacent to the AC terminal block The circuit breaker protects...

Страница 18: ...0Vac High line re connect 270Vac Max AC input voltage 300Vac rms Nominal input frequency 50Hz 60Hz Auto detection Low line frequency disconnect 40 1Hz High line frequency disconnect 65 1Hz Output volt...

Страница 19: ...Surge rating 10000VA Capable of starting electric motor 2 5HP Output short circuit protection current limit fault after 4 cycles max Bypass breaker size 40A Nominal DC input voltage 48V Min DC start v...

Страница 20: ...r charge protection Bat V 60Vdc Fault Buzzer alarm Charge algorithm Three stage Boost CC constant current stage Boost CV constant voltage stage Float constant voltage stage Battery type Setting 0 3v b...

Страница 21: ...ction DC input Shut down Shut down Recovery 2 Over Load Line 110 150 1beep 0 5s and Beep Manual Protection Inverter load continuous 10s continuous 150 load 1beep 0 5s and Beep continuous 5s continuous...

Страница 22: ...capability specified in the specs 2 Output short circuit 2 Check wiring or remove abnor mal load 3 Over temp 3 Move away barrier in front of airflow inlet 4 Over charger 4 Restart the unit 5 Over volt...

Страница 23: ...ial fault or damage as a result of failure of this appliance This guarantee does not affect your statutory or Common Law rights Returns Should your unit need repair the quickest and simplest way is to...

Страница 24: ...11 A I 10910152 the power to protec t Warranty Sollatek s warranty covers the Sollatek unit only and not any other equipment connected to it Sollatek will not accept any consequential loss or damage t...