Sollatek PowerBack PB5000 Скачать руководство пользователя страница 3

 

S o l l at e k   P o w e r B a c k   M a N U a l

       

3

PURPose 

this manual explains procedures for the unit’s installation, operation and troubleshooting 
Please take time to understand the contents of this manual prior to installation and operation.

IMPoRtAnt sAFetY InstRUCtIons

warNING: this chapter contains important safety and operating instructions. read and keep 

this User Guide for future reference. Display this notice at location of batteries.

General Precautions  

1.   Before using the unit, read all instructions and cautionary markings on: 
  the unit (2) the batteries (3) all appropriate sections of this manual. 

2.  CAUtIon

 -to reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries.

   other types of batteries may burst, causing personal injury and damage.

3.  Do not expose the unit to rain, snow or liquids of any type. the unit is designed for indoor use only.  
  Protect the unit from splashing if used in vehicle applications.

4.  Do not disassemble the unit. take it to a qualified Sollatek service center when service or repair is 
  required. Incorrect re-assembly may result in a risk of electric shock or fire.

5.  to reduce risk of electric shock, disconnect all wiring before attempting any maintenance or  
  cleaning. turning off the unit will not reduce this risk. 

WARnInG: WoRKInG In VICInItY oF A LeAD ACID BAtteRY Is DAnGeRoUs.

BAtteRIes GeneRAte eXPLosIVe GAses DURInG noRMAL oPeRAtIon

. Provide ventilation 

to outdoors from the battery compartment. the battery enclosure should be designed to prevent 
accumulation and concentration of hydrogen gas in “pockets” at the top of the compartment. Vent 
the battery compartment from the highest point. a sloped lid can also be used to direct the flow to 
the vent opening location.

7. 

neVeR

 charge a frozen battery.

8.  No terminals or lugs are required for hook-up of the ac wiring. 

ac wiring must be no less than 6mm csa (10 awG) gauge copper wire and rated for 75

º

c or 

higher. Battery cables must be rated for 75oc or higher and should be no less than 25mm csa 
(4awG). crimped and sealed copper ring terminal lugs with an 8mm (5/16) diameter hole should 
be used to connect the battery cables to the Dc terminals of the unit. Soldered cable lugs are also 
acceptable.

9.  Be extra cautious when working with metal tools on, or around batteries. the potential exists to  
  drop a tool and short-circuit the batteries or other electrical parts resulting in sparks that could  
  cause an explosion.

10. No ac or Dc disconnects are provided as an integral part of this unit.  Both ac and Dc disconnects  
  must be provided as part of the system installation. See INStallatIoN section of this manual.

11. No over current protection for the battery supply is provided as an integral part of this unit. over  
  current protection of the battery cables must be provided as part of the system installation. See  
  INStallatIoN section of this manual.

Содержание PowerBack PB5000

Страница 1: ...PowerBack PB5000 5KVA 220 230Vac 48Vdc INVERTER CHARGER USER MANUAL the power to protec t...

Страница 2: ...Cable Connection 9 AC Cable Size 10 AC Connections 11 AC Isolation and Overcurrent Protection 12 AC Loads 12 Protecting your PowerBack 12 Commissioning of PowerBack 12 OPERATION 13 Front Panel Control...

Страница 3: ...DANGEROUS BATTERIES GENERATE EXPLOSIVE GASES DURING NORMAL OPERATION Provide ventilation to outdoors from the battery compartment The battery enclosure should be designed to prevent accumulation and c...

Страница 4: ...ow a spark or flame in vicinity of a battery or generator 7 Be extra cautious when working with metal tools on and around batteries Potential exists to short circuit the batteries or other electrical...

Страница 5: ...only INSTALLATION Warning Installation must only be carried out by a competent person who has sufficient electrical training and is familiar with safe practices when working on or near electrical sys...

Страница 6: ...B a c k M A N U AL Figure 1 1 Utility Backup B A T T E R Y B A N K L O A D S A C P C T E L E V I S I O N H O M E E L E C T R O N I C S AC DISTRIBUTION PANEL U T I L I T Y S U P P L I E R TO PRIMARY S...

Страница 7: ...ble Energy Source S O L A R H Y D R O W I N D B A T T E R Y B A N K L O A D S A C R E F R I G E R A T I O N O F F I C E F A C T O R Y E L E C T R O N I C S M A I N S O R G E N E R A T O R S T A N D B...

Страница 8: ...t to allow adequate ventilation The unit has forced cooling and the fans operate full time Saver mode allow fans to turn off when no load applied Batteries must be installed in a dry shaded location T...

Страница 9: ...ce the ring terminal of DC cable over the bolt and directly against the unit s battery terminal Tighten the M8 screw to 5 8 Nm Do not place anything between the flat part of the Backup System terminal...

Страница 10: ...n lifting heavy items Caution Do NOT place anything between battery cable ring terminals and terminals on the inverter The terminal screw is not designed to carry current Apply Anti oxidant paste to t...

Страница 11: ...s isolated Turning off the PowerBack does not constitute disconnection from the battery Step 2 Feed the wires through cable clamp and AC cover See Figure 4 Figure 4 AC Cable Connections to unit Step 3...

Страница 12: ...or 40A advised depending on cable type selected installation method and ambient operating temperatures Consult with local regulations AC Loads The AC load or loads must be suitably protected with app...

Страница 13: ...ON Located on front of PowerBack PB5000 To de energise the PowerBack System Turn off PowerBack Switch off mains Open battery isolator fuse Turn on PowerBack for 30 seconds then back off to dissipate a...

Страница 14: ...nfiguration mode there are 4 configuration pages in total Turn page by pressing configuration button Page Description Selectable option 1 Input range Normal generator wide range 2 Output range 220v 23...

Страница 15: ...lays input voltage output voltage and load percentage information Inverter Mode Indicator The inverter mode symbol will appear and the indicator displays input voltage output voltage and load informat...

Страница 16: ...eft ON OFF OFF OFF OFF Low battery alarm flash OFF OFF OFF OFF 1beep 2s Low battery off flash OFF OFF OFF OFF Load indicator Indicates the load percentage in VA or W whichever is the higher the overlo...

Страница 17: ...r cycle will then reset Internal Circuit Breaker The unit contains one 40A input circuit breaker located on the rear panel of the chassis adjacent to the AC terminal block The circuit breaker protects...

Страница 18: ...0Vac High line re connect 270Vac Max AC input voltage 300Vac rms Nominal input frequency 50Hz 60Hz Auto detection Low line frequency disconnect 40 1Hz High line frequency disconnect 65 1Hz Output volt...

Страница 19: ...Surge rating 10000VA Capable of starting electric motor 2 5HP Output short circuit protection current limit fault after 4 cycles max Bypass breaker size 40A Nominal DC input voltage 48V Min DC start v...

Страница 20: ...r charge protection Bat V 60Vdc Fault Buzzer alarm Charge algorithm Three stage Boost CC constant current stage Boost CV constant voltage stage Float constant voltage stage Battery type Setting 0 3v b...

Страница 21: ...ction DC input Shut down Shut down Recovery 2 Over Load Line 110 150 1beep 0 5s and Beep Manual Protection Inverter load continuous 10s continuous 150 load 1beep 0 5s and Beep continuous 5s continuous...

Страница 22: ...capability specified in the specs 2 Output short circuit 2 Check wiring or remove abnor mal load 3 Over temp 3 Move away barrier in front of airflow inlet 4 Over charger 4 Restart the unit 5 Over volt...

Страница 23: ...ial fault or damage as a result of failure of this appliance This guarantee does not affect your statutory or Common Law rights Returns Should your unit need repair the quickest and simplest way is to...

Страница 24: ...11 A I 10910152 the power to protec t Warranty Sollatek s warranty covers the Sollatek unit only and not any other equipment connected to it Sollatek will not accept any consequential loss or damage t...

Отзывы: