Inverter Mode specifications
MoDeL
PB5000 (48V)
output voltage waveform
pure sine wave
rated output power(Va)
5000
Power factor
0.84
Nominal output voltage(V)
230Vac
output frequency(Hz)
50Hz / 60Hz ± 1Hz
output voltage regulation
±10% rms
Nominal efficiency
>90%
overload protection
fault after 5s@
≥
150% load,
fault after 10s@110%-150% load,
Surge rating
10000Va
capable of starting electric motor
2.5HP
output short circuit protection
current limit (fault after 4 cycles max)
Bypass breaker size
40a
Nominal Dc input voltage
48V
Min Dc start voltage
40V
low Dc alarm
42.0 ± 1.2Vdc
low Dc alarm recovery
43.2 ± 1.2Vdc
low Dc shut-down
40.0±1.2Vdc
low Dc shut-down recovery
44.0±1.2Vdc
High Dc Shut-down
60.0±1.2Vdc
High Dc shut-down recovery*
58.0±1.2Vdc
Power saver setting
0w (Set “oFF” at lcD)
10±5w enter 5+/-2w leave (Set “oN” at lcD)
*