Sollatek PowerBack PB5000 Скачать руководство пользователя страница 19

 

S o l l at e k   P o w e r B a c k   M a N U a l

       

1 9

 

Inverter Mode specifications

 

MoDeL 

PB5000 (48V) 

output voltage waveform 

pure sine wave

rated output power(Va) 

5000

Power factor 

0.84

Nominal output voltage(V) 

230Vac

output frequency(Hz) 

50Hz / 60Hz ± 1Hz

output voltage regulation 

±10% rms

Nominal efficiency 

>90%

overload protection 

fault after 5s@

150% load,

 

 

fault after 10s@110%-150% load,

Surge rating 

10000Va

capable of starting electric motor 

2.5HP

output short circuit protection 

current limit (fault after 4 cycles max)

Bypass breaker size 

40a

Nominal Dc input voltage 

48V 

Min Dc start voltage 

40V 

low Dc alarm 

42.0 ± 1.2Vdc 

low Dc alarm recovery 

43.2 ± 1.2Vdc 

low Dc shut-down 

40.0±1.2Vdc 

low Dc shut-down recovery 

44.0±1.2Vdc 

High Dc Shut-down 

60.0±1.2Vdc 

High Dc shut-down recovery* 

58.0±1.2Vdc 

Power saver setting 

0w (Set “oFF” at lcD)

10±5w enter  5+/-2w leave (Set “oN” at lcD)
 
 
 
*

Note: necessary condition for DC low recovery is: Line voltage must be available for charging.

Содержание PowerBack PB5000

Страница 1: ...PowerBack PB5000 5KVA 220 230Vac 48Vdc INVERTER CHARGER USER MANUAL the power to protec t...

Страница 2: ...Cable Connection 9 AC Cable Size 10 AC Connections 11 AC Isolation and Overcurrent Protection 12 AC Loads 12 Protecting your PowerBack 12 Commissioning of PowerBack 12 OPERATION 13 Front Panel Control...

Страница 3: ...DANGEROUS BATTERIES GENERATE EXPLOSIVE GASES DURING NORMAL OPERATION Provide ventilation to outdoors from the battery compartment The battery enclosure should be designed to prevent accumulation and c...

Страница 4: ...ow a spark or flame in vicinity of a battery or generator 7 Be extra cautious when working with metal tools on and around batteries Potential exists to short circuit the batteries or other electrical...

Страница 5: ...only INSTALLATION Warning Installation must only be carried out by a competent person who has sufficient electrical training and is familiar with safe practices when working on or near electrical sys...

Страница 6: ...B a c k M A N U AL Figure 1 1 Utility Backup B A T T E R Y B A N K L O A D S A C P C T E L E V I S I O N H O M E E L E C T R O N I C S AC DISTRIBUTION PANEL U T I L I T Y S U P P L I E R TO PRIMARY S...

Страница 7: ...ble Energy Source S O L A R H Y D R O W I N D B A T T E R Y B A N K L O A D S A C R E F R I G E R A T I O N O F F I C E F A C T O R Y E L E C T R O N I C S M A I N S O R G E N E R A T O R S T A N D B...

Страница 8: ...t to allow adequate ventilation The unit has forced cooling and the fans operate full time Saver mode allow fans to turn off when no load applied Batteries must be installed in a dry shaded location T...

Страница 9: ...ce the ring terminal of DC cable over the bolt and directly against the unit s battery terminal Tighten the M8 screw to 5 8 Nm Do not place anything between the flat part of the Backup System terminal...

Страница 10: ...n lifting heavy items Caution Do NOT place anything between battery cable ring terminals and terminals on the inverter The terminal screw is not designed to carry current Apply Anti oxidant paste to t...

Страница 11: ...s isolated Turning off the PowerBack does not constitute disconnection from the battery Step 2 Feed the wires through cable clamp and AC cover See Figure 4 Figure 4 AC Cable Connections to unit Step 3...

Страница 12: ...or 40A advised depending on cable type selected installation method and ambient operating temperatures Consult with local regulations AC Loads The AC load or loads must be suitably protected with app...

Страница 13: ...ON Located on front of PowerBack PB5000 To de energise the PowerBack System Turn off PowerBack Switch off mains Open battery isolator fuse Turn on PowerBack for 30 seconds then back off to dissipate a...

Страница 14: ...nfiguration mode there are 4 configuration pages in total Turn page by pressing configuration button Page Description Selectable option 1 Input range Normal generator wide range 2 Output range 220v 23...

Страница 15: ...lays input voltage output voltage and load percentage information Inverter Mode Indicator The inverter mode symbol will appear and the indicator displays input voltage output voltage and load informat...

Страница 16: ...eft ON OFF OFF OFF OFF Low battery alarm flash OFF OFF OFF OFF 1beep 2s Low battery off flash OFF OFF OFF OFF Load indicator Indicates the load percentage in VA or W whichever is the higher the overlo...

Страница 17: ...r cycle will then reset Internal Circuit Breaker The unit contains one 40A input circuit breaker located on the rear panel of the chassis adjacent to the AC terminal block The circuit breaker protects...

Страница 18: ...0Vac High line re connect 270Vac Max AC input voltage 300Vac rms Nominal input frequency 50Hz 60Hz Auto detection Low line frequency disconnect 40 1Hz High line frequency disconnect 65 1Hz Output volt...

Страница 19: ...Surge rating 10000VA Capable of starting electric motor 2 5HP Output short circuit protection current limit fault after 4 cycles max Bypass breaker size 40A Nominal DC input voltage 48V Min DC start v...

Страница 20: ...r charge protection Bat V 60Vdc Fault Buzzer alarm Charge algorithm Three stage Boost CC constant current stage Boost CV constant voltage stage Float constant voltage stage Battery type Setting 0 3v b...

Страница 21: ...ction DC input Shut down Shut down Recovery 2 Over Load Line 110 150 1beep 0 5s and Beep Manual Protection Inverter load continuous 10s continuous 150 load 1beep 0 5s and Beep continuous 5s continuous...

Страница 22: ...capability specified in the specs 2 Output short circuit 2 Check wiring or remove abnor mal load 3 Over temp 3 Move away barrier in front of airflow inlet 4 Over charger 4 Restart the unit 5 Over volt...

Страница 23: ...ial fault or damage as a result of failure of this appliance This guarantee does not affect your statutory or Common Law rights Returns Should your unit need repair the quickest and simplest way is to...

Страница 24: ...11 A I 10910152 the power to protec t Warranty Sollatek s warranty covers the Sollatek unit only and not any other equipment connected to it Sollatek will not accept any consequential loss or damage t...

Отзывы: