Installation must only be carried out by a competent person
who has sufficient electrical
training and is familiar with safe practices when working on or near electrical systems.
WARnInG: shock Hazard.
take appropriate safety measure when dealing with a battery terminal voltage exceeding
40Vdc.
WARnInG: short circuit hazard.
take special care not to short any battery terminal, shorting of battery terminals will produce
large currents and subsequent discharge of molten metals.
Sparks may cause ignition of battery gases if local ventilation is inadequate.
WARnInG: safe handling.
take appropriate safe handling measures when lifting heavy items.
Caution!
Do Not place anything between battery cable ring terminals and terminals on the inverter.
the terminal screw is not designed to carry current. apply anti-oxidant paste to terminals aFter
terminals have been tightened.
Caution!
ensure the batteries string circuit is disconnected until instructed to do so in the
commissioning procedure. Best practice is to remove the cable from the positive terminal of the
battery as well as operating the disconnection device.
AC Cable size
Before wiring the input and output of inverter, refer to table 2 for minimum recommended cable size
and torque value.
Model Number
ac Input (min)
ac output (min)
torque value
PB5000
6mm.10 awG
6mm csa. 10 awG
1.2-1.8 Nm
Min recommended cable size, torque value for AC wiring