5. Operation
5. Operation
The default protection settings and setting range for different regions are showing below:
Region
Australia A
Australia B
New Zealand
Australia C
Standard
Code Name
4777-A
4777-B
4777-C
4777-N
Setting Range
OV-G-V1
OV-G-V2
UN-G-V1
UN-G-V2
OV-G-F1
OV-G-F2
UN-G-F1
UN-G-F2
Startup-T
Recover-VH
Recover-FH
Start-VH
OVGV1-T
OVGV2-T
UNGV1-T
UNGV2-T
OVGF1-T
OVGF2-T
UNGF1-T
UNGF2-T
Restore-T
Recover-VL
Recover-FL
Start-VL
265V
275V
180V
70V
52HZ
52HZ
47HZ
47HZ
60S
253V
50.15Hz
1.5S
0.1S
10S
1.5S
265V
275V
180V
70V
52HZ
52HZ
47HZ
47HZ
60S
253V
50.15Hz
1.5S
0.1S
10S
1.5S
265V
275V
180V
70V
55HZ
55HZ
45HZ
45HZ
60S
253V
50.15Hz
1.5S
0.1S
10S
1.5S
265V
275V
180V
70V
55HZ
55HZ
45HZ
45HZ
60S
253V
50.15Hz
1.5S
0.1S
10S
1.5S
230-276V
230-276V
38-230V
38-230V
50-55HZ
50-55HZ
45-50HZ
45-50HZ
10-600S
230-276V
50-52Hz
1-2S
0.1-2S
10-11S
1-2S
0.1S
0.1S
1.5S
1.5S
60S
205V
47.5Hz
0.1S
0.1S
1.5S
1.5S
60S
205V
47.5Hz
0.1S
0.1S
5S
60S
205V
47.5Hz
0.1S
0.1S
1.5S
60S
196V
47.5Hz
0.1-2S
0.1-2S
1-6S
1-6S
10-600S
115-230V
47-50Hz
253V
253V
253V
253V
230-276V
205V
205V
205V
196V
115-230V
Start-FH
Start-FL
50.15Hz
50.15Hz
50.15Hz
50.15Hz
50-52Hz
47.5Hz
47.5Hz
47.5Hz
47.5Hz
47-50Hz
Table 5.1
5S
1.5S
This function is used to start or stop the generation of the inverter.
Figure 5.26 Set ON/OFF
5.6.2 ON/OFF
Settings
ON
/
OFF
2015-02-23 19 35
ON
OFF
Y E S
=
< E N T >
N O
=
< E S C >
STOP
Calibrate
2015-02-23 19 35
Total
Energy
Power
Parameter
5.6.3 Calibrate
By using our data monitoring hardware, the data on monitoring website can automatically
synchronize with the preset total generating power of inverter.
Warranty or maintenance may result in resetting total generating data, this function allow
the maintenance personnel to amend the total generating data of replacement inverter to
the original one.
Figure 5.27 Calibrate