6. Operation
6. Operation
.30.
6.4.7 Communication Data
The screen shows the internal data of the Inverter (see Figure 6.14), which is for service
technicians only.
01-05: 01 25 E4 9D AA
06-10: C2 B5 E4 9D 55
Figure 6.14 Communication Data
6.4.6 Daily Records
The screen shows history of changing settings. Only for maintance personel.
This function is used to select the grid's reference standard (see Figure 6.16).
YES=<ENT> NO=<ESC>
Standard:G59/3
Figure 6.16
NOTE:
This function is for technicians use only.
Press the UP/DOWN keys to select the standard (UL-240V-A, UL-208V-A, UL-240V,
UL-208V, R21P3-240, R21P3-208, ISONE240, ISONE208, R21P3-24A, R21P3-20A,
ISONE240A, ISONE208A, MEX-CFE , User-Def, etc.).
Press the ENTER key to confirm the setting.
Press the ESC key to cancel changes and returns to previous menu.
NOTE:
The default setting is 240V single phase “UL-240V” or “UL-240V-A”,
Otherwise, refer to local requirements.
6.5.1 Selecting Standard
6.5 Advanced Settings - Technicians Only
NOTE:
This area is for fully qualified and accredited technicians only.
Please follow 6.4 to enter password to access this menu.
There are 12 settings for USA and CSA market, UL-240V, UL-208V, R21P3-240, R21P3-208,
ISONE240 and ISONE208 are the settings for inverters without AFCI Function.
UL-240V-A, UL-208V-A, R21P3-24A, R21P3-20A, ISONE240A and ISONE208A are the
settings for inverters with AFCI Function. The default grid setting is 240V.
Selecting the “User-Def” menu will access to the following submenu (see Figure 6.17),
Figure 6.17
Below is the setting range for “User-Def”. Using this function, the limits can be changed
manually.
NOTE:
The " User-Def" function can be only used by the service engineer and
must be allowed by the providing utility.
OV-G-V1: 260V
OV-G-V1-T: 1S
6.4.8 Warning
Message
The display shows the
latest warning messages (see Figure 6.15). Screens can be scrolled
100
manually by pressing the UP/ DOWN keys. Press the ESC key to return to the previous
menu.
Msg000:
T: 00
-
00
00
:
00
D
:
0000
Figure 6.15 Warning Message
Select Advanced Settings from the Main Menu to access the following options:
1. Select Standard 2. Grid ON/OFF 3.Clear Energy 4. Reset Password
5. Power Control 6.Calibrate Energy 7.Special settings 8
.
STD. Mode Settings
9
.
Restore settings 10.HMI Update 11.Restart HMI 12.Debug Parameter
13.Compensation Set 14.DSP Update 15.External EPM Set
.31.
OV-G-V1: 220---300V OV-G-F1: 50.2-53Hz(60.2-63Hz)
OV-G-V1-T: 0.1---9S OV-G-F1-T: 0.1---9S
OV-G-V2: 220---300V OV-G-F2: 51-53Hz(61-63Hz)
OV-G-V2-T: 0.1---1S OV-G-F2-T: 0.1---9S
UN-G-V1: 110---210V UN-G-F1: 47-49.5Hz(57-59.5Hz)
UN-G-V1-T: 0.1---9S UN-G-F1-T: 0.1---9S
UN-G-V2: 110---210V UN-G-F2: 47-49Hz(57-59Hz)
UN-G-V2-T: 0.1---1S UN-G-F2-T: 0.1---9S
Startup-T
:
10-600S
Restore-T: 10-600S
→