6. Operation
6. Operation
.36.
Table
6
.
2
Voltage ride through
Wear
pressure
Region
1
2
3
4
5
Hv2
voltage
(
% nominal voltage
)
240Va.c.
V≥288
120≤V
<
168
/ /
12S
/ /
20S
Operating mode
Momentary
Cessation
Continuous
Operation
Mandatory
Operation
Maximum
time limit
0.16S
11S
13S
21S
/ /
6
V
<
120
1
.
5S
Hv1
NN
Lv1
Lv2
Lv3
208Va.c.
264
<
V
<
288
211.2≤V≤264
168≤V
<
211.2
V≥249.6
228.8
<
V
<
249.6
183.04≤V≤228.8
145.6≤V
<
183.04
104≤V
<
145.6
V
<
104
Ride-through
until
10S
1S
Not
Applicable
Mandatory
Operation
Momentary
Cessation
The voltage and frequency ride through limit is fixed.
6.5.7.9 IgZero_COMP.Set
6.5.7.10 PI Set
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
6.5.7.11 IgADCheckPRO Set
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
Figure 6.23 V/FRT Set
VRT
_
US
:
STOP
FRT
_
US
:
STOP
.37.
Solis US version inverters have Seven working modes:
1. NULL 2. Volt-watt 3. Volt-Var 4. Fixed-PF 5. Reac-power 6. Power-PF 7. VgWatt-UL
Based on UL1741SA, working mode 1,3,4,7 can be used by grid operator.
6.5.8 STD. Mode Settings
6.5.8.1 Working Mode Set
Q1
,
cap
Q2
=
Q3
=
0
Q4
,
ind
V1
V2
Vnom
V3
V4
Figure 6.24
Volt
-
VAR curve for Q
(
V
)
6.5.8.1.1 With UL Standard selected
1.
Working Mode Set 2.
Power Rate Limit 3.
Freq Derate Set 4.
10mins Voltage Set
5.
Power Priority 6.
Initial Settings 7.
Voltage PCC Set 8.
Freq-Watt
Selecting “STD Mode. Settings” displays the sub-menu shown below:
2. Volt-Watt (Not Required)
Description: Inverter will change the active output power based on voltage change.
Note: This Setting is NOT required by UL1741SA Standards.
1.NULL
Description: Inverter is not under any working mode.
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
3. Volt-Var (Default)
Description: Inverter will change the reactive output power based on voltage change.
There are TWO situations with different grid standards selected.
NOTE:
The following modes are for "UL-480V", "UL-480V-A".