5.2 AC Connection
5.2.1 AC Side Requirements
①
An independent AC breaker is required in both on-grid and back-up
output side, and any loads cannot be connected with inverter directly.
②
Before making the connection of AC cable, please confirm all DC &
AC power source are disconnected from the inverter.
③
The Solinteg MHS-3~8kW series single-phase high voltage hybrid
inverter applies to the single-phase power grid with a voltage of 230V
and a frequency of 50/60Hz.
④
Connect the inverter to the grid only after getting an approval from
the local electric power company.
NOTICE
A single-phase AC breaker needs to be installed on the AC side of the MHS-3~8kW. To en-
sure that the MHS-3~8kW can safely disconnect itself from the power grid when an excep-
tion occurs, select a proper overcurrent protection device in compliance with local power
distribution regulations and Max. input (output) current of MHS-3~8kW AC side.
The allowable AC cable of wire diameter and cross-sectional area for Solinteg MHS-3~8kW
are as shown in the following:
Figure 5-4
On-grid side uses a three-core cable (L, N, and PE). Back-up side uses a two-core cable (L, N).
Determine whether an AC circuit breaker with greater overcurrent
capacity is required based on actual conditions.
NOTICE
Wire Diameter:13-18mm
Strip Length:10mm
50mm