61
User Manual
MHS-3~8K
series
※ 7.4 Country Code (Safety Code) Setting
Please set "Country code (Safety code)" under the menu "Safety Set" in " Advanced
Settings ".
Refer to “7.3 Advanced Setting” for more information.
※
7.5 Auto-Test
This function is disabled by default, and will be only functional in the safety code of Italy.
Short press the button several times until "Auto Test CEI 0-21" displays on the screen,
press and hold the button 3 seconds to activate “Auto Test". After the auto test is finished,
short press the button several times until the screen displays "Auto Test Record", and hold
the button 3 seconds to check the test results.
The auto test will start when the correct test item is selected, and the test result will be
displayed on the screen when it finished. If the test was successful, it will display "Test
Pass", otherwise will display "Test Fail”. After each item tested, the inverter will reconnect
to the grid and automatically start the next test according to the requirements of CEI
0-21.
Abbreviation
Complete Name
SOC Reset
If turned it on, the battery will be automatically charged to calibrate the battery SOC.
After the battery is charged, this function will be turned off automatically
MPPT Parallel
If MPPT is connected in parallel, enable this function.
MaxOutputSet
Select the maximum AC output power.
Rated, Max. output power= Rated output power on the datasheet
Overload, Max. output power= Max. output power on the datasheet
Limit, Max. output power
<
Rated output power on the datasheet
Export Control
In the power export limit on mode, when the communication between the inverter
and meter or the inverter and datalogger is interrupted, select the inverter operation
mode from one of the follows:
Hard, inverter stops
Soft, inverter generates power as the “Feed in Grid” value set on the screen
Содержание MHS-3.6K-30
Страница 1: ......
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 19: ...19 User Manual MHS 3 8K series D E F G H I A B C Figure 3 5 Packing list J K L User Manual ON GRID BACK UP ...
Страница 85: ......
Страница 86: ......
Страница 87: ......
Страница 88: ...www solinteg com M11 00008 00 ...