- 12-
3.5.2 Inspection before Start up
1) Mechanical Inspection:
a. Check the cabinet and inside pipe system for possible damage during transportation.
b. Check that the heating water circuit is filled and well vented. Check the pipe system for leaks.
c. Check the Fan making sure it can move freely.
2) Electric System Inspection
a. Check the power supply (voltage/frequency) matches the rating label and specification.
b. Check all the electrical connections for loose or damaged wires due to transportation.
3) Pipe Inspection
a. Check all the valves, and water flow directions.
b. Check for any possible leaks inside or outside of unit.
c. Check the insulation of all the pipes.
3.5.3 Start up and Commissioning
a. After the system inspection is finished, startup can begin.
b. Connect the power supply; switch on the isolator to turn on the heat pump.
c. The circulation pumps starts immediately. After 30 seconds, the fan motor starts. After another 10
seconds, compressor starts.
d. Air is initially released from the hot water and venting may be necessary. If bubbling sounds can be
heard from the heat pump, the circulation pump or radiators the entire system will require further venting.
When the system is stable (correct pressure and all air eliminated) the automatic heating control system
can be set as required.
e. Check heating water inlet/outlet temperature difference after the system is stable.
f. Check the compressor exhaust and suction temperature.
g. Adjust the parameters according to different weather conditions and user requirements.
4 CONTROLLER MANUAL
4.1 Electric Parts Control Program working theory
a) Compressor
After the compressor is shut down, it has a minimum interval of 3 minutes before the next start up
The initial "power-up" does not require the protection of three minutes;
During defrost, compress on/off interval is based on the defrost parameters.
b) Start up / Shut down Cycle
When the heat pump switches on, the water circulation pump and the fan will start 60 seconds before
compressor
When the heat pump switches off, the water circulation pump shuts down 30 seconds after the
compressor. The fan switches off 5 seconds after the compressor
During defrost, the water circulation pump does not stop running;
c) DHW Auxiliary Electric Heater E1
F08=0, E1 is not valid ; F08=1,E1 is valid.
E1
turns on as set out in the conditions below:
Ambient temperature ≤ set value (parameter F09,-20°C ~ 30°C, default 0°C);
Содержание GAG-08DC
Страница 1: ... 1 DC INVERTER AIR TO WATER HEAT PUMP User Manual Model GAG 08DC 12DC 16DC ...
Страница 6: ... 6 B Space Heating Cooling Mode Only C 2x8 12 16 Installation Space Heating Cooling DHW ...
Страница 7: ... 7 D 3x8 12 16 Installation Space Heating Cooling DHW Solar Application 1 ...
Страница 10: ... 10 Wiring Diagram GAG 16DC ...
Страница 27: ... 27 5 2 System Drawing 5 3 Dimensions mm GAG 08DC ...
Страница 28: ... 28 GAG 12DC GAG 16DC ...