E01/HP
High pressure switch off
1.Refrigerant volume too much 2.throtting part error
3. pressure switch fault.
E02
High pressure protection
1.Refrigerant volume too much 2.throtting part error
3. High pressure switch fault.
E03/LP
Low pressure switch off
1.Refrigerant volume too little 2.throtting part error
3. pressure switch fault.
E04
Low pressure protection
1.Refrigerant volume too little 2.throtting part error
3. Low pressure switch fault.
E06
Over current protection
Compressor current is too high
E08
High
discharge
temperature
protection
1.Refrigerant volume too little 2.throtting part error
3.discharge temperature sensor fault.
E09
Discharge sensor error
Temp sensor open circuit or short circuit
E10
Suction temperature sensor error
Temp sensor open circuit or short circuit
E11
Coil temperature sensor error
Temp sensor open circuit or short circuit
E12
Outdoor air temp sensor error
Outdoor air temp sensor open circuit or short circuit
E14
Inlet water temp sensor error
Temp sensor open circuit or short circuit
E15
DHW temp sensor error
Temp sensor open circuit or short circuit
E16
Outlet water temp sensor error
Temp sensor open circuit or short circuit
E17/FLO
Water flow error
1.Water flow volume too small 2. Water flow switch error
E18
Ambient temp too low
1.Outdoor air temp too low
2.temp sensor error
En
Communication error
Communication wire open or PCB error
E20
Miss/Wrong phase
Power supply error
E22
Password valid
E23
Memorizer error
PCB fault
E38
Temperature difference too high
Temperature difference between inlet and outlet water is
too high
E84
voltage protection
Voltage is too high or too low, heat pump will recover when
voltage be normal (165~265VAC)
E85
Voltage too high
Voltage≥265VAC
E86
Voltage too low
Voltage≤165 VAC
E97
DC Voltage too high
DC Voltage ≥ VDC
E98
DC Voltage too low
Voltage ≤ VDC
E99
Phase current too high
Phase current ≥ A
E100
DC motor out of step
DC motor out of step
E101/E102
Compressor Miss phase
Compressor connection line fault
E103/E103
IPM Error
IPM fault
E108
IPM temperature abnormity
IPM temperature sensor fault
E111
IPM doesn’t match compressor
IPM fault
E113/E114
PFC error
IPM fault
E116
PFC over current
IPM fault
E117
DC voltage abnormity
DC Voltage
E118
AC voltage too low
Voltage≤165 VAC
Содержание GAG-08DC
Страница 1: ... 1 DC INVERTER AIR TO WATER HEAT PUMP User Manual Model GAG 08DC 12DC 16DC ...
Страница 6: ... 6 B Space Heating Cooling Mode Only C 2x8 12 16 Installation Space Heating Cooling DHW ...
Страница 7: ... 7 D 3x8 12 16 Installation Space Heating Cooling DHW Solar Application 1 ...
Страница 10: ... 10 Wiring Diagram GAG 16DC ...
Страница 27: ... 27 5 2 System Drawing 5 3 Dimensions mm GAG 08DC ...
Страница 28: ... 28 GAG 12DC GAG 16DC ...