- 21-
F36
Difference between ambient and coil temperature
to active defrost( -7°C ≤Ambient temp ≤3°C)
0~25°C
6
°C
F37
Compressor discharge air protection temp
(higher than the setting, it will protect)
90~130°C
115
°C
F38
Compressor protection current
3-35A
12A
F39
Compressor 0 A current test
0: no test ;1: test
0
F40
Limited frequency current
F42
Ambient temperature to active compressor heater
-20~30°C
7
°C
F43
Maximum outlet water temp to stop compressor
30~100°C
75
°C
F44
Minimum outlet water temp to stop compressor
-40~35°C
3
°C
F45
Difference between inlet and outlet water temp
to stop compressor
0: no stop;1~25 :stop
0
F53
Ambient temperature to stop heat pump
-40~40°C
-40°C
F54
AC maximum temperature
25~100°C
55°C
F55
AC minimum temperature
3~25°C
10°C
F56
DHW maximum temperature
0~80°C
50°C
F58
EC motor speed (80=maximum
speed X80%;0=maximum speedX40%)
0-10
80
F59
How many compressors
0-255
0
F60
Maximum frequency(cooling)
20-100
70
F61
Maximum frequency(heating)
20-100
75
F62
Maximum frequency(DHW)
20-100
75
F63
Minimum frequency(cooling)
20-50
30
F64
Minimum frequency(healing)
20-50
30
F65
Defrost frequency
20-100
60
F67
EEV Temp differential to stop the valve(heating)
-20~20°C for factory only
2°C
F68
EEV temp differential to stop the valve (cooling)
-20~20°C for factory only
2°C
F69
EEV control mode
0~15
12
F70
EEV minimum steps/2
0~100
35
F71
Cooling mode and Ambient temp=5°C,EEV steps
15~250
100
F72
Cooling mode and Ambient temp=15°C,EEV steps
15~250
140
F73
Cooling mode and Ambient temp=25°C,EEV steps
15~250
160
F74
Cooling mode and Ambient temp=35°C,EEV steps
15~250
180
F75
Numbers of steps of EEV per adjustment
0~10
2
F76
Heating mode and Ambient temp=0°C,EEV steps
15~250
100
F77
Heating mode and Ambient temp=10°C,EEV steps
15~250
140
F78
Heating mode and Ambient temp=20°C,EEV steps
15~250
160
F79
Heating mode and Ambient temp=30°C,EEV steps
15~250
180
F80
Numbers of steps of EEV per adjustment
0~10
2
F84
Running frequency setting
0-20(0:test mode;1:fixed frequency;2:Auto frequency) 2
F85
Running with fixed frequency (for factory
testing only)
20~120 HZ
50HZ
F86
Resonance frequency (High)
0~100
0
F87
Resonance frequency (Low)
0~100
0
F92
Water flow switch type
0:water flow switch; 1:DN15 flow meter; 2:DN20
flow meter; 3:DN25 flow meter
3
F93
Minimum water flow
1-200L/min
12
Содержание GAG-08DC
Страница 1: ... 1 DC INVERTER AIR TO WATER HEAT PUMP User Manual Model GAG 08DC 12DC 16DC ...
Страница 6: ... 6 B Space Heating Cooling Mode Only C 2x8 12 16 Installation Space Heating Cooling DHW ...
Страница 7: ... 7 D 3x8 12 16 Installation Space Heating Cooling DHW Solar Application 1 ...
Страница 10: ... 10 Wiring Diagram GAG 16DC ...
Страница 27: ... 27 5 2 System Drawing 5 3 Dimensions mm GAG 08DC ...
Страница 28: ... 28 GAG 12DC GAG 16DC ...