7. Module protection (H5):

Handling method:

Check if the voltage between power module P and N is too low and
if the current is too high. In normal condition, voltage between P and

 N should be about 320V.

Normal

Abnormal

Check power supply circuit of outdoor unit (if PTC resistance

rectifying bridge, reactor, capacitance etc. is ok).

Temperature of power module is too high, 

which  causes overheating protection

Protection is still displayed

Confirm the setting status of outdoor unit (cooling)

Normal

Confirm if outdoor fan motor is running; unplug the 

three connecting wires between U, V, W of compressor 

and power module. Turn on the unit to see if outdoor 

fan runs normally (about 1 minute)

Outdoor fan stops 

Measure the voltage of outdoor

fan connector

No voltage

Normal voltage 

Replace the fan

Replace the mainboard 

motor

of outdoor unit

Check if radiating paste is spread 

evenly or radiating sticker is stuck

 well; if screws of power module 

is tightened

 Reinstall power module and 

 re-spread radiating paste or 

stick radiating sticker on the

 radiator of power module.

Poor radiation, heat exchanger

 is dirty

Remove obstructions 
and clean

Outdoor fan runs 

Confirm if there is voltage output and balance of 

voltage between any two phases of U, V and W. 

Yes

No

Whether module type 

Replace the power module 

is correct

Normal

Abnormal

Normal

Abnormal

Measure the three-phase 

Replace the module 

with correct type

resistance of compressor

Replace the 

Whether cylinder of 

compressor is stuck 

compressor

If the unit runs normally after connected 
with the new compressor for trial run, the 

 cylinder of original compressor is stuck 

4

2

Содержание KFHHP-12

Страница 1: ...1 Summary and features Model Remarks KFIHP 09 SOLEUSAIR 1Ph 115V 60Hz R410A KFHHP 12 1Ph 208 230V 60Hz R410A...

Страница 2: ...ng Motor W Fuse A Sound Pressure Level dB A H M L Dimension W D H in Dimension of Package W D H in Net Weight Gross Weight lb Model KFIHP 09 Function Rated Voltage 115V Frequency Hz 60HZ Rated Capacit...

Страница 3: ...Excessive Operating Pressure for the Suction Side MPa Sound Pressure Level dB A H M L Dimension W D H in Dimension of Package W D H mm Net Weight Gross Weight lb Refrigerant Charge oz Length ft Gas ad...

Страница 4: ...A Sound Pressure Level dB A H M L Dimension W D H in Dimension of Package W D H in Net Weight Gross Weight lb Model KFHHP 12 Function Rated Voltage 208V 230V Frequency Hz 60HZ Rated Capacity Btu h Ra...

Страница 5: ...ng Pressure for the Suction Side MPa Sound Pressure Level dB A H M L Sound Power Level dB A H M L Dimension W D H in Dimension of Package W D H mm Net Weight Gross Weight lb Refrigerant Charge oz Leng...

Страница 6: ...jsf Bjs Pvumfu 8 Part name Indoor Unit Outdoor Unit Air inlet Wireless remote controll Front panel Guide louver Air outlet Receiving window LED board wrapping tape Air inlet Air outlet Drainage hose C...

Страница 7: ...4 Air inlet grill Right piping hole Left piping hole Top view Unit mm Rear view Wall mounting plate Overall and Installing Dimension UOverall and Installing Dimension of Indoor Unit SOLEUSAIR 9...

Страница 8: ...UOverall and Installing Dimension of Outdoor Unit Nut Bolt Wrench Unit mm 10...

Страница 9: ...INDOOR UNIT Circuit Diagram These circuit diagrams are subject to change without notice Please refer to the ones stuck on the machines SOLEUSAIR KFIHP 09 11...

Страница 10: ...INDOOR UNIT OUTDOOR UNIT 5 Circuit Diagram These circuit diagrams are subject to change without notice Please refer to the ones stuck on the machines SOLEUSAIR KFHHP 12 12...

Страница 11: ...Tset 3min Compressor Outdoor fan Indoor fan Start cooling Original running state Stop cooling Set fan speed Run Stop 6 1 2 1 2 Protection function Antifreezing protection Under cooling and drying mod...

Страница 12: ...stop In this mode the temperature setting range is 16 30 The air conditioner will adjust the running frequency of the compressor automatically according to the change of ambient temperature When the u...

Страница 13: ...et temperature will be increased or decreased by 1 Adjusting range is 16 30 In AUTO mode this button does not function 6 1 3 4 AUTO key When the unit is stop press AUTO key the unit will run under AUT...

Страница 14: ...Set temperature Timing etc Under turn on state when power off and power on the power supply for outdoor unit will be turn on after 3mins Under turn off state when power off and power on the power supp...

Страница 15: ...you can use panel support bar to support the panel Screw off the fixing screws of the electric box cover and open the electric box top cover to take it off As shown in Fig 7 1 Panel panel sup port ba...

Страница 16: ...overs Fig 7 4 Disassembling the electric box cover Unloose the 3 clasps to take off the electric box cover As shown in Fig 7 5 cl clasps Fig 7 5 Fig 7 6 Fig 7 7 Disassembling the water tray assy Unloo...

Страница 17: ...arward to let out the side clasps of the evaporator from the groove Take out the evaporator carefully and pay attention to protecting the connecting pipe 7 1 9 Disassembling the motor Screw off the 3...

Страница 18: ...sassemble Rear Grill Top Cover Handle screw screw Figure 7 13 Screw out the 4 self tapping screws on rear side plate and chassis of valve supporter and side plate of condenser can take off rear grill...

Страница 19: ...igure 7 16 7 17 electric box cover bolts Figure 7 16 Figure 7 17 bolts Disassemble Right Side Plate Screw out the 5 bolts on rear side plate can take off right side plate refer to Figure 7 18 bolts Fi...

Страница 20: ...to wrap the 4 way valve unsold the four soldering points connecting the 4 way valve and remove the 4 way valve Be quick during the unsoldering process pay attention to keep the wrapping cloth wet and...

Страница 21: ...being harmed by high temperature Unscrew the two screws fixing the small valve unsolder the soldering point connecting the small valve and the fork type pipe and remove the small valve refer to Figur...

Страница 22: ...8 Exploded View and Components and Parts List Exploded View of Components and Parts of Indoor Unit SOLEUSAIR KFIHP 09 KFHHP 12ID 26...

Страница 23: ...ontrol 30511010 1 17 Light Cover 22242031 1 18 Display Board 30545706 1 19 Display Cover 20 Shield Board 26112044 1 21 Guide Louver 26112033 1 22 Guide Louver 26112034 1 23 Step Motor 15212110 1 24 Ri...

Страница 24: ...ight Cover 22242031 1 18 Display Board 30545557 1 19 Display Cover 22432071 1 20 Shield Board 26112048 1 21 Guide Louver 26112043 1 22 Guide Louver 26112042 1 23 Step Motor MP28EA 15212105 1 24 Right...

Страница 25: ...Exploded View of Outdoor unit KFIHP 09OD 30...

Страница 26: ...03023670 1 20 Electric Cover Assy 01413086 1 21 4 way Valve Coil 430004002 1 22 capacitor clamp 1 23 capacitor 1 24 Terminal Board A 42010255 1 25 Electric Box 2 01413025 1 26 electrical filter 1 27...

Страница 27: ...Exploded View of O u tdoor Unit KFHHP 12OD 34...

Страница 28: ...way Rever sing Valve Component 03023670 1 20 Electric Cover Assy 01413086 1 21 4 way Valve Coil 430004002 1 22 Terminal Board A 42010255 1 23 Electric Box 2 01413025 1 24 Electric Box 20113001 1 25 PC...

Страница 29: ...The controller is broken Batteries of remote controller are low Malfunction of remote controller Loose or poor connection of receiving head Receiving head is broken Measure the insulating resistance...

Страница 30: ...hick pipe and thin pipe are insulated well The exposed part of the connector and copper pipe must be insulated as well Heat exchanger of outdoor unit is blocked Air filters are blocked Fan speed is se...

Страница 31: ...ard and module Abnormal input of power module Abnormal output of power module Compressor temperature is too high Wrong wiring Damage of outdoor main control board Check the circuit according to circui...

Страница 32: ...ainage hose Re wrap and make it tight Adjust fan location Take out the foreign substance Adjust support washer of the compressor and tighten loose bolts Separate the touched pipeline 1 Tighten connect...

Страница 33: ...mal IPM module protection corresponds to H5 of indoor unit Overcurrent protection corresponds to E5 of indoor unit Overload protection corresponds to H4 of indoor unit Discharge protection corresponds...

Страница 34: ...unction of protector Handling method adjust refrigerant amount replace the capillary replace the compressor use universal meter to check if the contactor of compressor is fine when it is not overheate...

Страница 35: ...the voltage of outdoor fan connector No voltage Normal voltage Replace the fan Replacethemainboard motor of outdoor unit Check if radiating paste is spread evenly or radiating sticker is stuck well if...

Отзывы: