6.1.3.7 Indoor fan control 
Use the remote controller to set the indoor fan running at HIGH, MED or LOW speed. At this time the fan will run 
at high,  medium or low speed. It can also be set to AUTO and the indoor fan will select fan speed(HIGH, MED or

 LOW) automatically  according to ambient temperature. 

 There are at least 3mins and 30s delay for fan speed shift.

6.1.3.8 Power supply for outdoor unit 

The power supply for outdoor unit is turned on in AUTO, COOL, HEAT and DRY mode under turn-on state. 
The power supply for outdoor unit will delay 3 minutes to turn off under turn-off state or in the FAN mode under

turn-on state. 

6.1.3.9 Swing control 

Use the SWING button of the wireless remote control to control SWING On and Off. Swing will only act when

indoor fan is running.After power on, the swing motor turns back to 0 position and closes the air outlet vent; if it 

does not preset swing, after the unit is turned on, it will turn to the max. air outlet D1 position; then turn back to  L

position under COOL mode.Under HEAT mode,the guide louver stays at D1;when in swinging state, it will swing

between L1 and D1 position. When the unit is turned off, it will turn back to 0 position.

6.1.3.10 Buzzer control

When the unit is power on or receives remote control signal or the auto key be pressed,the buzzer will give out a beep.

6.1.3.11 Power-off memory function 

Contents of memory: Mode; Swing; Set fan speed, Set temperature,Timing  etc.
Under turn-on state, when power off and power on, the power supply for outdoor unit will be turn on after 3mins .
Under turn-off state, when power off and power on, the power supply for outdoor unit will be turn on immediately.

6.1.3.12 Delay Protection of  Compressor

Under  COOL; DRY; HEAT mode, before each time the compressor starts,  there will be 3mins delay. 
6.1.4. Common protection function in each mode
6.1.4.1 Overload protection

T

tube

:at cooling,it detects the temp. of outdoor heat exchanger,at heating,it detects the temp. of indoor heat exchanger.

When Ttube is detected high, the compressor will run in limited frequency.When Ttube goes on rising over the stated 

value, the compressor will stop, under AUTO HEAT or HEAT mode, indoor fan will blow 60s at low fan speed and

then stop, under other mode, the indoor fan will run at set speed.
6.1.4.2 Compressor discharge temperature protection 
When discharge temperature is too high to over the stated value, the compressor will stop, and When discharge temp.

resume normal and the compressor has stopped  for 3 minutes, the unit will resume its original operating status. 

6.1.4.3 Communication malfunction

When not receiving correct signal for 3 minutes, the unit has communication malfunction and the outdoor unit 

stops, it is the same as normal stop when meeting the set temp..

6.1.4.4 Module protection

When module is in protection, the compressor will stop, after the compressor has stopped  for 3 minutes, it will 

resume to running. During module protection period, the indoor unit displays malfunction and the whole unit stops. 

SOLEUSAIR

18

Содержание KFHHP-12

Страница 1: ...1 Summary and features Model Remarks KFIHP 09 SOLEUSAIR 1Ph 115V 60Hz R410A KFHHP 12 1Ph 208 230V 60Hz R410A...

Страница 2: ...ng Motor W Fuse A Sound Pressure Level dB A H M L Dimension W D H in Dimension of Package W D H in Net Weight Gross Weight lb Model KFIHP 09 Function Rated Voltage 115V Frequency Hz 60HZ Rated Capacit...

Страница 3: ...Excessive Operating Pressure for the Suction Side MPa Sound Pressure Level dB A H M L Dimension W D H in Dimension of Package W D H mm Net Weight Gross Weight lb Refrigerant Charge oz Length ft Gas ad...

Страница 4: ...A Sound Pressure Level dB A H M L Dimension W D H in Dimension of Package W D H in Net Weight Gross Weight lb Model KFHHP 12 Function Rated Voltage 208V 230V Frequency Hz 60HZ Rated Capacity Btu h Ra...

Страница 5: ...ng Pressure for the Suction Side MPa Sound Pressure Level dB A H M L Sound Power Level dB A H M L Dimension W D H in Dimension of Package W D H mm Net Weight Gross Weight lb Refrigerant Charge oz Leng...

Страница 6: ...jsf Bjs Pvumfu 8 Part name Indoor Unit Outdoor Unit Air inlet Wireless remote controll Front panel Guide louver Air outlet Receiving window LED board wrapping tape Air inlet Air outlet Drainage hose C...

Страница 7: ...4 Air inlet grill Right piping hole Left piping hole Top view Unit mm Rear view Wall mounting plate Overall and Installing Dimension UOverall and Installing Dimension of Indoor Unit SOLEUSAIR 9...

Страница 8: ...UOverall and Installing Dimension of Outdoor Unit Nut Bolt Wrench Unit mm 10...

Страница 9: ...INDOOR UNIT Circuit Diagram These circuit diagrams are subject to change without notice Please refer to the ones stuck on the machines SOLEUSAIR KFIHP 09 11...

Страница 10: ...INDOOR UNIT OUTDOOR UNIT 5 Circuit Diagram These circuit diagrams are subject to change without notice Please refer to the ones stuck on the machines SOLEUSAIR KFHHP 12 12...

Страница 11: ...Tset 3min Compressor Outdoor fan Indoor fan Start cooling Original running state Stop cooling Set fan speed Run Stop 6 1 2 1 2 Protection function Antifreezing protection Under cooling and drying mod...

Страница 12: ...stop In this mode the temperature setting range is 16 30 The air conditioner will adjust the running frequency of the compressor automatically according to the change of ambient temperature When the u...

Страница 13: ...et temperature will be increased or decreased by 1 Adjusting range is 16 30 In AUTO mode this button does not function 6 1 3 4 AUTO key When the unit is stop press AUTO key the unit will run under AUT...

Страница 14: ...Set temperature Timing etc Under turn on state when power off and power on the power supply for outdoor unit will be turn on after 3mins Under turn off state when power off and power on the power supp...

Страница 15: ...you can use panel support bar to support the panel Screw off the fixing screws of the electric box cover and open the electric box top cover to take it off As shown in Fig 7 1 Panel panel sup port ba...

Страница 16: ...overs Fig 7 4 Disassembling the electric box cover Unloose the 3 clasps to take off the electric box cover As shown in Fig 7 5 cl clasps Fig 7 5 Fig 7 6 Fig 7 7 Disassembling the water tray assy Unloo...

Страница 17: ...arward to let out the side clasps of the evaporator from the groove Take out the evaporator carefully and pay attention to protecting the connecting pipe 7 1 9 Disassembling the motor Screw off the 3...

Страница 18: ...sassemble Rear Grill Top Cover Handle screw screw Figure 7 13 Screw out the 4 self tapping screws on rear side plate and chassis of valve supporter and side plate of condenser can take off rear grill...

Страница 19: ...igure 7 16 7 17 electric box cover bolts Figure 7 16 Figure 7 17 bolts Disassemble Right Side Plate Screw out the 5 bolts on rear side plate can take off right side plate refer to Figure 7 18 bolts Fi...

Страница 20: ...to wrap the 4 way valve unsold the four soldering points connecting the 4 way valve and remove the 4 way valve Be quick during the unsoldering process pay attention to keep the wrapping cloth wet and...

Страница 21: ...being harmed by high temperature Unscrew the two screws fixing the small valve unsolder the soldering point connecting the small valve and the fork type pipe and remove the small valve refer to Figur...

Страница 22: ...8 Exploded View and Components and Parts List Exploded View of Components and Parts of Indoor Unit SOLEUSAIR KFIHP 09 KFHHP 12ID 26...

Страница 23: ...ontrol 30511010 1 17 Light Cover 22242031 1 18 Display Board 30545706 1 19 Display Cover 20 Shield Board 26112044 1 21 Guide Louver 26112033 1 22 Guide Louver 26112034 1 23 Step Motor 15212110 1 24 Ri...

Страница 24: ...ight Cover 22242031 1 18 Display Board 30545557 1 19 Display Cover 22432071 1 20 Shield Board 26112048 1 21 Guide Louver 26112043 1 22 Guide Louver 26112042 1 23 Step Motor MP28EA 15212105 1 24 Right...

Страница 25: ...Exploded View of Outdoor unit KFIHP 09OD 30...

Страница 26: ...03023670 1 20 Electric Cover Assy 01413086 1 21 4 way Valve Coil 430004002 1 22 capacitor clamp 1 23 capacitor 1 24 Terminal Board A 42010255 1 25 Electric Box 2 01413025 1 26 electrical filter 1 27...

Страница 27: ...Exploded View of O u tdoor Unit KFHHP 12OD 34...

Страница 28: ...way Rever sing Valve Component 03023670 1 20 Electric Cover Assy 01413086 1 21 4 way Valve Coil 430004002 1 22 Terminal Board A 42010255 1 23 Electric Box 2 01413025 1 24 Electric Box 20113001 1 25 PC...

Страница 29: ...The controller is broken Batteries of remote controller are low Malfunction of remote controller Loose or poor connection of receiving head Receiving head is broken Measure the insulating resistance...

Страница 30: ...hick pipe and thin pipe are insulated well The exposed part of the connector and copper pipe must be insulated as well Heat exchanger of outdoor unit is blocked Air filters are blocked Fan speed is se...

Страница 31: ...ard and module Abnormal input of power module Abnormal output of power module Compressor temperature is too high Wrong wiring Damage of outdoor main control board Check the circuit according to circui...

Страница 32: ...ainage hose Re wrap and make it tight Adjust fan location Take out the foreign substance Adjust support washer of the compressor and tighten loose bolts Separate the touched pipeline 1 Tighten connect...

Страница 33: ...mal IPM module protection corresponds to H5 of indoor unit Overcurrent protection corresponds to E5 of indoor unit Overload protection corresponds to H4 of indoor unit Discharge protection corresponds...

Страница 34: ...unction of protector Handling method adjust refrigerant amount replace the capillary replace the compressor use universal meter to check if the contactor of compressor is fine when it is not overheate...

Страница 35: ...the voltage of outdoor fan connector No voltage Normal voltage Replace the fan Replacethemainboard motor of outdoor unit Check if radiating paste is spread evenly or radiating sticker is stuck well if...