Marine Diesel gensets. Operator’s Manual.
Installation
Section 3
–
Installation
3.1.
Angle of Installation
Make sure the genset is installed on a level surface. Otherwise, the following angular operation
maximum is permitted:
Continuously
Temporary
29 GSC / 32 GSAC / 35 GTC / 40 GTAC / 45 GTC / 54
GTAC / 50 GTC / 60 GTAC / 68 GTC / 84 GTAC
15º
25º (max. 30 min.)
If the genset operates in these conditions, check
Section 5.4. Lubrication System
.
3.2.
Genset installation
Follow these steps to install the genset:
1.
Fix genset.
See 9.4 Genset Dimensions
(mounting holes) and
Section 8 Tightening Torques
.
2.
Connect exhaust outlet. See
9.4 Genset Dimensions
.
1.
Wet exhaust outlet
2.
Dry exhaust Seawater outlet
3.
Connect siphon breaker. (If installed) See
9.4 Genset Dimensions and 5.7 Inlet and exhaust
system
.
4.
Connect sweater inlet. See
9.4 Genset Dimensions
.
5.
Connect fuel inlet. See
9.4 Genset Dimensions
.
6.
Connect leak coolant outlet. See
9.4 Genset Dimensions
.
7.
Fill the lubrication circuit with an adequate oil. See
5.4 Lubrication System
.
8.
Fill the cooling circuit with an adequate coolant. See
5.6 Cooling System
.
9.
Check each pipe connection for oil or coolant leaks.
10.
Connect to earth. See
5.5 Fuel System
.
11.
Prime the fuel system. See
5.5 Fuel System
.
12.
Connect to control panel. See Section
9.4 Genset Dimensions
.
13.
Connect to the battery. Follow label battery connection into the genset.
It is necessary to install a waterlock (supplied as accessory) in the exhaust system to avoid
water ingestion (See
5.7 Inlet and exhaust system
).