![Solcon MPS 3000 Скачать руководство пользователя страница 65](http://html1.mh-extra.com/html/solcon/mps-3000/mps-3000_manual_1314378065.webp)
TECHNICAL SPECIFICATIONS
Page 65 of 67
Total Run Time
Accuracy:
±2%.
Current Unbalance Alarm and Trip
Method:
Unbalance = 100 * (Negative Sequence Current / Positive Sequence Current) [%]
If Motor Load < 100% then multiply by * (Motor Load / 100)
This is to prevent nuisance tripping at low current levels.
Level 1
Threshold Unbalance Level 1: 50% of Unbal Current setting ± 2%.
Alarm (fixed) time delay: 1.0 ± 0.5 Sec.
Level 2 Curves
Threshold Unbalance Level 2: Unbal Current setting ± 2%.
Trip time accuracy: ± 1 second up to 10 seconds.
± 1 /- 2% above 10 seconds.
Fault Time Delays
Accuracy:
±0.5 Sec. or ±2% of time, which ever is greater, for all but the above mentioned faults and
the following exceptions:
* Overcurrent Level 2: When adjusted to 0 >>> 60 ms +/- 20 ms. -0.1/+0.2 Sec. up to 1
Sec.
* Ground fault trip: -0.1/+0.2 Sec. for less than 1 Sec. delay.
Relays Contacts
Rated load:
8A/250 VAC 1800VA.
Maximum voltage:
250VAC.
Dielectric Strength
1500 VAC, for 1 minute, Between Ground (terminal 63) and:
*
Current inputs.
*
Auxiliary power supply inputs
*
Voltage inputs.
*
Control terminals
Power and Reactive Power Measurements
Method:
True RMS over three phase voltages and currents.
Range :
0.1 KW - 30MW (0.1 KVAR - 30 MVAR)
Full Scale :
30MW (30 MVAR)
Resolution :
0.1 KW below 1 MW, 0.01 MW above 1 MW.
Accuracy :
For V
≥
90 * VT Primary / VT Secondary & Power factor
≥
0.5, with three phase voltages.
Two Ranges :
1. For (10% < I
≤
150%) of "C/T" primary, accuracy is :
± (2% + 0.01 * "C/T" Primary/ Motor FLC.) of motor rated Power
2. For ( I
≥
150%) of "C/T" primary, accuracy is :
± 7% of the display reading
Power Factor
Method:
Ratio between total power (P) to total apparent power (VA).
Range :
0.0 - 1.0 leading / lagging.
Resolution :
0.001
Accuracy :
For V
≥
90 * VT Primary / VT Secondary & I
≥
50% of "C/T" Primary & Power factor
≥
0.7
it is ± 0.03
Ambient Temperature
0°C to +50°C
Содержание MPS 3000
Страница 1: ...MPS 3000 MOTOR PROTECTION SYSTEM Version 18 7 2006...
Страница 7: ...WIRING DIAGRAM MPS3000 Page 7 of 67 WIRING DIAGRAM MPS3000...
Страница 8: ...WIRING DIAGRAM MPS3000 C Page 8 of 67 WIRING DIAGRAM MPS3000 C...
Страница 9: ...REAR PANEL MPS3000 and MPS3000 C Page 9 of 67 REAR PANEL MPS3000 and MPS3000 C...
Страница 66: ...TECHNICAL SPECIFICATIONS Page 66 of 67 CASE AND CUTOUT DETAILS...