![Solcon MPS 3000 Скачать руководство пользователя страница 39](http://html1.mh-extra.com/html/solcon/mps-3000/mps-3000_manual_1314378039.webp)
SET PAGE - MENUS
Page 39 of 67
0 % of FLC
Range: 0..200 (Units change with parameter).
Anlog Out 2 Max.
200 % of FLC
Value for maximum (20mA, or 1mA by special order) output.
Range: 0..250 (Units change with parameter).
Anlog Out 3 Par.
Thermal capacity
Analog 3 output parameter.
Range: Same as for Anlog Out 1 par.
Anlog Out 3 Min.
0 % of FLC
Value for zero (0 or 4mA) output.
Range: 0..200 (Units change with parameter).
Anlog Out 3 Max.
200 % of FLC
Value for maximum (20mA, or 1mA by special order) output.
Range: 0..250 (Units change with parameter).
Anlog Out 4 Par.
MAX OF T1..T3
Analog 4 output parameter.
Range: Same as for Anlog Out 1 par.
Anlog Out 4 Min.
0 °C
Value for zero (0 or 4mA) output.
Range: 0..200 (Units change with parameter).
Anlog Out 4 Max.
200 °C
Value for maximum (20mA, or 1mA by special order) output.
Range: 0..250 (Units change with parameter).
Anlog In 1 Type
4..20mA
Selects between 0..20mA (or 0..1mA by special order) and 4..20mA analog input
type.
Range: 0..20mA (0..1mA by special order), 4..20mA..
Anlog In 1 Level.
Above 50%
Fault Level. Fault occurs when input is Above (or Below, if set so) Anlog In 1 Level
for more than Anlog In 1 Delay.
Range: Below 0..100%, Above 1..100%.
Anlog In 1 Delay
10 Sec.
Time Delay for Analog Input 1 Fault.
Range: 0..250 Sec.
Anlog In 2 Type
4..20mA
Selects between 0..20mA (or 0..1mA by special order) and 4..20mA analog input
type.
Range: 0..20mA (0..1mA by special order), 4..20mA..
Anlog In 2 Level.
Above 50%
Fault Level. Fault occurs when input is Above (or Below, if set so) Anlog In 2 Level
for more than Anlog In 2 Delay.
Range: Below 1..100%, Above 1..100%.
Anlog In 2 Delay
10 Sec.
Time Delay for Analog Input 2 Fault.
Range: 0..250 Sec.
Anlog In 3 Type
4..20mA
Selects between 0..20mA (or 0..1mA by special order) and 4..20mA analog input
type.
Range: 0..20mA (0..1mA by special order), 4..20mA..
Anlog In 3 Level.
Above 50%
Fault Level. Fault occurs when input is Above (or Below, if set so) Anlog In 3 Level
for more than Anlog In 3 Delay.
Range: Below 1..100%, Above 1..100%.
Anlog In 3 Delay
10 Sec.
Time Delay for Analog Input 3 Fault.
Range: 0..250 Sec.
Anlog In 4 Type
4..20mA
Selects between 0..20mA (or 0..1mA by special order) and 4..20mA analog input
type.
Range: 0..20mA (0..1mA by special order), 4..20mA..
Anlog In 4 Level.
Above 50%
Fault Level. Fault occurs when input is Above (or Below, if set so) Anlog In 4 Level
for more than Anlog In 4 Delay.
Range: Below 1..100%, Above 1..100%.
Anlog In 4 Delay
10 Sec.
Time Delay for Analog Input 4 Fault.
Range: 0..250 Sec.
Содержание MPS 3000
Страница 1: ...MPS 3000 MOTOR PROTECTION SYSTEM Version 18 7 2006...
Страница 7: ...WIRING DIAGRAM MPS3000 Page 7 of 67 WIRING DIAGRAM MPS3000...
Страница 8: ...WIRING DIAGRAM MPS3000 C Page 8 of 67 WIRING DIAGRAM MPS3000 C...
Страница 9: ...REAR PANEL MPS3000 and MPS3000 C Page 9 of 67 REAR PANEL MPS3000 and MPS3000 C...
Страница 66: ...TECHNICAL SPECIFICATIONS Page 66 of 67 CASE AND CUTOUT DETAILS...