MPS3000 TERMINALS
Page 15 of 67
MPS3000-C special use:
The relays can be configured with contactors control functions which may be required, according to the control
application.
Output A Relay:
Can be configured as one of:
* DOL starting
* Star period of Star-Delta starting
* Forward of a forward-reverse motor
* High speed of two-speed motor
Output B Relay:
Can be configured (by parameter setting) as one of the following functions:
* Delta period of Star/Delta starting
* Reverse of a forward-reverse motor
* Low speed of two-speed motor
Output C Relay:
Can be configured (by parameter setting) as one of the following functions:
* Contactor A status.
* Contactor B status.
* Start/Run - controls line contactor in Star-Delta starters.
Serial Link
Standard RS485 Half Duplex, with MODBUS protocol.
Twisted shielded pair should be used for wiring
.
Shield should be connected to Chassis Ground externally,
near the MPS3000.
Acceptable baud rates: 1200, 2400, 4800, 9600 and 19200 BPS.
Serial Port (+)
.........................................
23
Serial Port (-)
.........................................
22
Serial Port (shield)
.................................
63
Notes:
1. Auxiliary Power Supply must power-cycled after changing communication's settings (e.g. baud-
rate).
2. Connect 120 Ohm resistors between (+) and (-) at the end and at the beginning of the line.
Содержание MPS 3000
Страница 1: ...MPS 3000 MOTOR PROTECTION SYSTEM Version 18 7 2006...
Страница 7: ...WIRING DIAGRAM MPS3000 Page 7 of 67 WIRING DIAGRAM MPS3000...
Страница 8: ...WIRING DIAGRAM MPS3000 C Page 8 of 67 WIRING DIAGRAM MPS3000 C...
Страница 9: ...REAR PANEL MPS3000 and MPS3000 C Page 9 of 67 REAR PANEL MPS3000 and MPS3000 C...
Страница 66: ...TECHNICAL SPECIFICATIONS Page 66 of 67 CASE AND CUTOUT DETAILS...