PE Connection and Leakage Current

•  

All inverters incorporate a certified internal Residual Current Device(RCD) in

   order to protect against possible  electrocution and fire hazard in case of a 
   malfunction in the PV array, cables or inverter. There are 2 trip thresholds for
   the RCD as required for certification (IEC 62109-2:2011). The default value for
   electrocution protection is 30 mA, and for slow rising current is 300 mA.
•  If an external RCD is required by local regulations, check which type of RCD is
   required for relevant electric code. It recommends using a type-A RCD. The 
   recommended RCD values is 100 mA or 300 mA unless a lower value is required
   by the specific local electric codes. When required by local regulations, the use
   of an RCD type B is permitted.

High leakage current!
Earth connection essential before connecting supply.

•  Incorrect grounding can cause physical injury, death or equipment malfunction
   and increase electromagnetic.
•  Make sure that grounding conductor is adequately sized as required by safety
   regulations.
•  Do not connect the ground terminals of the unit in series in case of a multiple
   installation. This product can cause current with a d.c. component. Where a residual
   current operated protective (RCD) or monitoring (RCM) device is used for protection
   in case of direct or indirect contact, only an RCD or RCM of type B is allowed
   on the supply side of this product.

  

For United Kingdom

•   The installation that connects the equipment to the supply terminals shall 
    comply with the requirements of BS 7671.
•   Electrical installation of PV system shall comply with requirements of BS 7671 
    and IEC 60364-7-712.
•   No protection settings can be altered.
•   User shall ensure that equipment is so installed, designed and operated to
    maintain at all times compliance with the requirements of ESQCR22(1)(a). 

  

For Australia and New Zealand

•   Electrical installation and maintenance shall be conducted by licensed 
electrician and shall comply with Australia National Wiring Rules.

09

08

2.3  Explanation of Symbols 

 

This section gives an explanation of all the symbols shown on the inverter and
on the type label.

Symbols on the Inverter

Symbol

Explanation

Operating Display.

An error has occurred, please inform your installer immediately.

Symbols on the Type Label

Safety

Safety

Symbol

Explanation

CE mark.
The inverter complies with the requirements of the applicable 
CE guidelines.

RCM remark.

Beware of hot surface.

The inverter can become hot during operation. Avoid contact 

during operation.

Danger of high voltages.
Danger to life due to high voltages in the inverter!

Danger.
Risk of electric shock!

Observe enclosed documentation.

The inverter can not be disposed together with the household waste. 
Disposal information can be found in the enclosed documentation.

Do not operate this inverter until it is isolated from mains 
and on-site PV generation suppliers.

Danger to life due to high voltage.

There is residual voltage in the inverter which needs 5 min to 

discharge.

•  Wait 5 min before you open the upper lid or the DC lid.

TUV certification.

Compliant with UKCA standards

.

Compliant with UKNI standards

.

RoHS certificate

The inverter complies with the requirements of Restriction of

Hazardous Substances.

Warning

!

Содержание X3-PRO G2 Series

Страница 1: ...on or individual should not plagiarize partially or fully copy including software etc and no reproduction or distribution of it in any form or by any means shall be allowed All rights reserved SolaX P...

Страница 2: ...Inverter 3 3 Dimension 4 Technical Data 4 1 DC Input 4 2 AC Output 4 3 Efficiency Safety and Protection 4 4 General Data 5 Installation 5 1 Check for Transport Damage 5 2 Packing List 5 3 Installatio...

Страница 3: ...ation appear in this document as described below 1 Notes on this Manual 7 Troubleshooting 7 1 Trouble Shooting 7 2 Routine Maintenance 8 Decommissioning 8 1 Dismantling the Inverter 8 2 Packaging 8 3...

Страница 4: ...rator if the voltage protection level VP of the surge arresters is greater than 1100V an additional SPD type 3 required surge protection for electrical devices 05 04 Safety Safety Anti Islanding Effec...

Страница 5: ...nstructions on obtaining service Attempting to service the X3 PRO G2 Series inverter yourself may result in a risk of electric shock or fire and will void your warranty Keep away from flammable explos...

Страница 6: ...irements of BS 7671 Electrical installation of PV system shall comply with requirements of BS 7671 and IEC 60364 7 712 No protection settings can be altered User shall ensure that equipment is so inst...

Страница 7: ...ulations Compliance with safety regulations depends upon installing and configuring system correctly including using the specified wires The system must be installed only by professional assemblers wh...

Страница 8: ...RS485 AC connector Pocket WiFi LAN optional 4G optional 482 00 mm 417 00 mm 186 00 mm 417 00 mm X3 PRO 12K G2 2D Ground connection port G 25500 1100 650 160 980 400 850 32 32 40 40 200 2 A 2 B 2 X3 P...

Страница 9: ...K G2 2D X3 PRO 10K G2 2D X3 PRO 15K G2 2D X3 PRO 12K G2 2D 99 90 97 80 98 30 X3 PRO 25K G2 3D X3 PRO 30K G2 3D 99 90 98 00 98 50 14 15 99 90 97 80 98 30 99 90 97 80 98 30 Technical Data Technical Data...

Страница 10: ...onal 1 M N PV pin contact positive 4 negative 4 for two strings positive 6 negative 6 for three strings Terminal block 1 RJ45 connector 1 F F 4 1 X3 PRO 8K G2 2D X3 PRO 10K G2 2D X3 PRO 15K G2 2D X3 P...

Страница 11: ...thin 5 5 4 Installation Steps Preparation Below tools are needed before installation Installation Installation The wall hanging the inverter should meet conditions below 1 solid brick concrete or stre...

Страница 12: ...eat dissipation The distance of installation space for multiple inverters is as follows Step 1 Fix the bracket to the wall First find the expansion screws and the bracket in the accessory bag as shown...

Страница 13: ...agon wrench to tighten them c Expansion bolts Rubber hammer d Self tapping screw Outer hexagonal wrench Gasket Step 3 Tighten the inverter and bracket f Use the inner hexagonal wrench to tighten the i...

Страница 14: ...Main Steps to Connect to the Inverter Inverter BMU Installation Installation Model Danger Danger to life due to high voltage on DC conductors when exposed to sunlight the PV array generates dangerous...

Страница 15: ...h indicates that the connection is completed Step 6 Tighten the fastening head and insert into the corresponding positive and negative PV PV ports of the inverter Step 4 Tighten the PV pin contact and...

Страница 16: ...5 6 mm 8 10 mm c Fetch the AC waterproof cover from the carton e Strip 82 mm of insulation from the cable ends by using the stripping pliers Micro breaker 16 A 32 A 50 A 2 5 5 mm 3 6 mm 3 6 mm 3 6 mm...

Страница 17: ...operating time of the fuses is less than 5 seconds installation method B2 according to 60204 1 2006 annex D cable in conduit EN cable trunking system number of loaded circuit only one Use H07 cord RN...

Страница 18: ...ebsite via connecting Pocket WiFi Pocket LAN can be purchased from the supplier for optional if needed Connection steps Please check the Pocket WiFi user manual for more details This is a communicatio...

Страница 19: ...Pin Definition 1 2 3 4 5 6 7 8 X X Heat Pump Controller X X X X b Dry Contact is provided to control the closing and breaking of switches by giving control signals as below c Heat Pump Controller is...

Страница 20: ...disconnected with grid If the Pocket WiFi is connected to the port please remove the Pocket WiFi at first 3 Then insert the U disk into the Dongle port on the bottom of the inverter Then turn on DC sw...

Страница 21: ...er starting up successfully Waiting Inverter is waiting to checking when DC input voltage from panels is greater than 160 V lowest start up voltage but less than 200 V lowest operating voltage Checkin...

Страница 22: ...n 2021 01 01 00 00 Enter Back U1 0 0V Down Up errors were kept English German XXXXXXXXXXXXXX User can see the U I F of the grid Ua Ia Fa Ub Ib Fb Uc Ic Fc Pout Pgrid Export Control DRM Function Grid S...

Страница 23: ...V Stage3 287 5 103 5 103 5 P freq Back Back Enter Up Down Enter Back Proportion x xx Up Down Grid Protection Enter Back Enable Freq ROCOF T_Start Up Down Up Down Up Down 60s H LVRT Function Disable U...

Страница 24: ...interface Level 1 is the default interface the inverter will automatically jump to this interface when the system started up successfully or not operated for a period of time The interface shows the...

Страница 25: ...an UserDefined option which allows the user to customize relevant parameters within a wider range b Export Control With this function the inverter can control energy exported to the grid Whether havi...

Страница 26: ...n in curve A For E 8001 curve cos f P should refer to curve B Default values of setting are as shown in curve B Reactive power control Reactive standard curve Q f V Q V Qmax Qmax V2s V1s V1i V2i V2i 0...

Страница 27: ...aving factory according to safety rules If reset is needed any changes should be made according to the requirements of local grid h Mppt Scan Mode There are four modes to be selected off low freq scan...

Страница 28: ...ent Dry Contact Load Management Disable Manual Smart Save Enter Back n PV Connection The user can select the PV connection type by this function Mode Select Mode Select Multi Comm o Nline Control The...

Страница 29: ...age Out of Normal Range Check if the PV input voltage is within the operating range of the inverter Disconnect PV wiring and reconnect Or seek help from us 54 Faults Diagnosis and Solution GridVolt10M...

Страница 30: ...n the rear of the inverter are covered by dirt and the machine should be cleaned and absorbed dust when necessary This work shall be performed from time to time 2 Check that if the indicators of the i...

Страница 31: ...h as earthquake flooding thunderstorm lighting fire hazard volcanic eruption etc Inverter s warranty is expired and doesn t buy extended warranty Can t provide the inverter s SN warranty card or invoi...

Страница 32: ...Module Brand Module Size W Number of String Number of Panel Per String Battery Type Brand Number of Battery Attached Battery If Any Module If Any Date of Delivery Signature Please visit our warranty w...

Страница 33: ...YOUR INVERTER ONLINE WIN SOLAX POINTS Open your camera app and point your device at the QR code Wait for the camera to recognize the QR code Click banner or noti cation when it appears on the screen W...

Отзывы: