Troubleshooting
Troubleshooting
●
If the information panel of your inverter does not show the Fault light, check the
following list to make sure that the present state of the installation allows proper
operation of the unit.
— Is the inverter located in a clean, dry, adequately ventilated place?
— Have the DC input breakers been opened?
— Are the specification and length of the cables suitable?
— Are the input and output connections and wiring in good condition?
— Are the configuration settings correct for your particular installation?
— Are the display panel and the communications cable properly
connected and undamaged?
7.2 Routine maintenance
Contact SolaX Customer Service for further assistance. Please be prepared to
describe details of your system installation and provide model and serial number
of the unit.
►
Safety checks
Safety checks should be performed at least every 12 months by manufacturer's
qualified person who has adequate training, knowledge, and practical
experience to perform these tests. The data should be recorded in an
equipment log. If the device is not functioning properly or fails any of test, the
device has to be repaired. For safety check details, refer to this manual, section 2
Safety instruction and CE Directives.
►
Maintain periodically
Only qualified person may perform the following works.
During the process of using the inverter, the manage person shall examine
and maintain the machine regularly. The concrete operations are as follows.
1: Check that if the cooling fins on the rear of the inverter are covered by
dirt, and the machine should be cleaned and absorbed dust when
necessary. This work shall be performed from time to time.
2: Check that if the indicators of the inverter are in normal state, check if the
keys of the inverter are in normal state, check if the display of the inverter is
normal. This check should be performed at least every 6 months.
3: Check that if the input and output wires are damaged or aged. This check
should be performed at least every 6 months.
4: Clean the inverter panels and check their security. This should be carried
out at least every 6 months.
56
57
Regular safety check and maintenance are required.
Faults
Diagnosis and Solution
EepromFault
DSP EEPROM Fault.
-Disconnect PV wiring and reconnect.
-Or seek help from us.
RcDeviceFault
Residual Current Device Fault.
-Restart the inverter.
-Update the ARM software or reburn the program.
-Or seek help from us.
PvConnDirFault
PV Direction Fault.
-Check if the PV+/- sides are connected correctly.
-Or seek help from us.
GridRelayFault
Relay Fault.
-Check the grid connection.
-Restart the inverter.
-Or seek help from us.
OtherDeviceFault
Model Incorrectly Set Fault.
-Seek help from us.
Mgr EEPROM Fault
ARM EEPROM Fault.
-Disconnect PV and grid, then reconnect.
-Or seek help from us.
Meter Fault
Meter Fault.
-Check the connection of the meter.
-Check if the meter is in working order.
-Or seek help from us.
Fan1 Warning
External Fan 1 Abnormal Warning.
-Check if the fan is working.
-Or seek help from us.
Fan2 Warning
External Fan 2 Abnormal Warning.
-Check if the fan is working.
-Or seek help from us.
PowerTypeFault
Power Type Fault.
-Check the version of ARM and DSP.
-Check the product SN number.
-Or seek help from us.