3. Product Information
4. Preparation before Installation
3.4
Specifications
3.4.1
T-BAT-SYS-HV
Configuration List
Note:
①
Test conditions: 100% DOD, 0.2C charge & discharge @+ 77°F/25°C.
②
90% DOD; System usable energy may vary with inverter different setting.
③
Discharge: In case of the battery core's temperature range of 14°F~41°F/-10°C~5°C and
113°F~127.4°F/45°C~53°C, the discharge current will be reduced; Charge: In case of the
battery core's temperature range of 32°F~68°F/0°C~20°C and 113°F~127.4°F/45°C~53°C,
the charge current will be reduced. Product charge or discharge power depends on the
actual temperature of the battery pack.
④
The battery can only be discharged and cannot be charged at -14°F~32°F/-10°C~0°C.
3.4.2
Performance Parameters
Q.+ BAT-G1
Nominal Voltage (Vdc)
Operating Voltage (Vdc)
Nominal Capacity (Ah)
Max. Charge/Discharge Current (A)
Recommend Charge/Discharge Current (A)
Standard Power (kW)
Max. Power (kW)
153.6
135-174
100
54
50
7.68
9.2
Battery Roundtrip Effciency(0.2C,
25°C/77°F)
Expected Lifetime
(25°C/77°F)
Cycle Life
90% DOD
(25°C/77°F)
95%
10 years
6000 cycles
Model
Nominal Energy (kWh)
15
Usable Energy 90% DOD (kWh)
13.8
90-116
100
54
50
5.12
6.1
102.4
10
9.2
180-232
100
54
50
12.3
20
18.4
204.8
10.24
①
①
②
③
Storage Temperature
Ingress Protection
IP65
-4°F~122°F/-20°C~50°C (3 months)
32°F~104°F/0°C~40°C (12 months)
Charge Temperature
Discharge Temperature
32°F~127.4°F/0°C~53°C
-14°F~127.4°F/-10°C~53°C
④
④
T-BAT H 10.0
T-BAT H 15.0
T-BAT H 20.0
Model
BMS
TBMS-MCS60060×1
Battery Module
TP-HS50 × 2
Energy(kWh)
10
15
20
Voltage (V)
90-116
135-174
180-232
TP-HS50 × 3
TP-HS50 × 4
T-BAT H 10.0
T-BAT H 15.0
T-BAT H 20.0
TBMS-MCS60060×1
TBMS-MCS60060×1
No.
1
2
3
4
Prepration before Installation
4.1
Prerequisites
When assembling the system, avoid touching the battery terminals with any metal
object or bare hands. According to the design principles, T-BAT-SYS-HV will
provide a safe and reliable energy. Improper operation and equipment damage may
cause overheating and electrolyte leakage. Therefore, the above-mentioned safety
precautions and warning information mentioned in this part shall be strictly
observed. If you have any question, please contact customer service. The “2
Safety” does not contain the provisions of all laws and regulations at the place
where the user located.
Before installation, make sure that the installation site meets the following
conditions:
Ÿ
The building can stand up to earthquakes;
Ÿ
The floor shall be flat;
Ÿ
No inflammable and explosive goods are placed within at least of 3 ft/0.91
m;
Ÿ
The temperature and humidity remain at a constant level;
Ÿ
The installation site requires less dust and dirt; and
Ÿ
There are no corrosive gases, including ammonia and acid vapor.
Ÿ
The site shall be over 0.62 miles/997.79 m away from the sea, to avoid damage
caused by salt water and humidity;
Ÿ
The ambiance shall be shady and cool, away from heat sources and direct
sunlight;
NOTE!
If the ambient temperature exceeds the operating range, the battery
pack will stop running to protect itself. The optimal temperature range
for running is 59°F/15°C to 86°F/30°C. Frequent exposure to harsh
temperatures may deteriorate the performance and lifetime of the
battery.