Solas PV-800HZ Скачать руководство пользователя страница 9

 

VERTICAL (THROUGH ROOF) VENTING 

INSTALLATION 

All part numbers in the following section are shown 

in Fig. #6. 

1.

 

Place the flashing (Part A) onto the chase and 

seal using silicone. 

2.

 

Put a bead of silicone on the underside of the 

vertical standoff (Part B) and place it on top 

of the flashing. Align the eight holes and 

secure both parts to the chase using eight #8 

x 1 1/2" screws provided. 

3.

 

Install the drip shield (Part C) onto the top of 

the vertical standoff using a bead of silicone 

between the two. Do not screw this part in 

place.  

4.

 

Bring the 14-2 electrical wire (not supplied) 

up through the holes in both the flashing and 

the drip shield leaving at least 12" of excess 

wire above the drip shield. 

5.

 

IMPORTANT: Attach an appropriate length(s) 

of the vent to the power vent terminal, 

sufficient to pass through the chase. Note: do 

not connect an adjustable length vent pipe 

to the terminal. 

Note: do not connect an adjustable length 

vent pipe to the terminal. 

6.

 

Seal the connection of the first length of pipe 

at the terminal and any other pipe to pipe 

joint by both screwing and taping the outside 

joint using high temperature foil tape. 

7.

 

Remove the junction box cover. (Part D) 

8.

 

Remove and discard the exhaust shield. (Part 

E) 

9.

 

Apply a bead of silicone on the “Part A 

Flashing” of the power vent terminal (HRD-

850V) 

10.

 

Slide the vent through the drip shield and at 

the same time thread the electrical lead 

through the hole in the bottom of the 

terminal. 

each side of the vertical standoff, the drip shield and 

the power vent terminal and then screw them 

together using the eight #8 x 1/2" stainless screws 

provided. 

12.

 

Join the 14-2 wire lead to the blower wires 

using the appropriate connectors and attach 

the ground wire. Reinstall the junction box 

cover. 

13.

 

Install the vertical rain cap (Part F) over the 

power vent blower. ALIGN THE EXHAUST 

OUTLET ON THE POWER VENT TERMINAL 

WITH THE EXHAUST PORT ON THE VERTICAL 

RAIN CAP. 

14.

 

Secure the vertical rain cap to the power vent 

blower with the remaining eight #8 x 1/2" 

stainless screws. 

Note: there are no pilot holes in the base of the 

power vent terminal. 1/8" diameter pilot holes 

should be drilled using the holes in the vertical 

rain cap as a guide.  
Do not silicone the vertical rain cap to the power 

vent terminal as it needs to be removable for 

servicing. 

15.

 

Attach the vent adaptor directly to the 

appliance with three screws and seal outer 

pipe with aluminum tape provided. 

Note: 

The inner pipe does not need to be sealed.

 

16.

 

Connect the high temperature silicone tube 

to the vacuum pressure tap on the adaptor, 

secure with the hose clamp provided and 

route the tube through any hole back to 

Pressure Switch. (Fig. #5) 

Note: Ensure that 

there are no blockages in this tube, as this 

will cause the control to malfunction.

 

17.

 

Run the required M&G Duravent GS / Secure 

Vent / Selkirk Direct-temp pipe from the 

adaptor to the terminal assembly. Assemble 

as per the vent pipe manufacturer’s 

instructions. 

Содержание PV-800HZ

Страница 1: ...S SEE THRU MODELS BI 48 ST BI 60 ST BI 72 ST SINGLE SIDE MODELS BI 48 SSL BI 48 SSR BI 60 SSL BI 60 SSR BI 72 SSL BI 72 SSR DIRECT VENT POWER VENT KIT PART PV 800HZ AND PV 850V Report 0361GF006S Ce ma...

Страница 2: ...cal Instructions 15 Replacement Parts List 16 Warranty Information 17 WE STRONGLY SUGGEST THAT YOU READ THIS MANUAL THOROUGHLY BEFORE BEGININNG THE INSTALLATION OF THE S LAS POWER VENT KIT THIS SPECIF...

Страница 3: ...D 804 POWER VENT CONTROL W PRESSURE SWITCH 1 10 HRD 852V OPTIONAL VERTICAL TERMINATION HARDWARE KIT 1 This kit uses either M G Duravent direct vent pipe Secure Vent direct vent pipe or Selkirk Direct...

Страница 4: ...rom the center line of the regulator I clearance to service regulator vent outlet 6 feet 1 8 m minimum J clearance to non mechanical air supply inlet to building or the combustion air inlet to any oth...

Страница 5: ...4...

Страница 6: ...ion of rise and run between the figures including up to 3 ft below the unit Figure 2 WARNING A minimum clearance to combustibles of 1 5 38mm is required around the vent pipe at all times Failure to ma...

Страница 7: ...he outer flanges that are used to secure the terminal to the building are covered by the exterior wall or siding Fig 4 Note No other part of the terminal can be recessed into the exterior wall or sidi...

Страница 8: ...7 Figure 5...

Страница 9: ...time thread the electrical lead through the hole in the bottom of the terminal each side of the vertical standoff the drip shield and the power vent terminal and then screw them together using the eig...

Страница 10: ...9 11 With the power vent terminal resting on the drip shield align the eight holes in...

Страница 11: ...10 VERTICAL THROUGH ROOF VENTING Final Installation Height 21 Figure 6...

Страница 12: ...essure switch requires a positive pressure of 0 05 W C to confirm the power vent is running There are 2 female connectors on the bottom surface of the power vent control enclosure as shown above The l...

Страница 13: ...ff the unit Connect the pressure tap on the vent adapter to the light grey port on the control using the pressure switch tubing HRD 806 provided Tape all seams in the venting system using Aluminum Foi...

Страница 14: ...the power vent relay harness HRD 803 to the AUX port on the fireplace control Connect the red wire spade connector from the power vent relay harness HRD 803 Cut the Red TC spade connector off Crimp o...

Страница 15: ...14 Disconnect the Red TC spade connector...

Страница 16: ...e fireplace is enclosed WARNING All electrical shall be completed by a licensed Electrician and must conform with local building code Improper installation may result in property damage injury or loss...

Страница 17: ...TIONAL VERTICAL TERMINATION CAP 1 4 HRD 803 POWER VENT RELAY HARNESS 1 9 HRD 851V OPTIONAL VERTICAL TERMINATION BOX 1 5 HRD 804 POWER VENT CONTROL W PRESSURE SWITCH 1 10 HRD 852V OPTIONAL VERTICAL TER...

Страница 18: ...Over firing operation above the listed BTU rate of this appliance can cause serious damage and will nullify this warranty This warranty is void if a The unit has been operated in atmospheres contamin...

Страница 19: ...18 c Any damage to the unit combustion chamber heat exchanger or other components due to water or weather damage which is the result of but not limited to improper chimney venting installation...

Страница 20: ...19...

Страница 21: ...20 V1 2 26 16...