HORIZONTAL (SIDE WALL) VENTING
This kit uses either Simpson Duravent GS direct vent pipe, Secure Vent direct vent pipe or Selkirk
Direct-temp vent pipe with a 4" inner pipe and a 6" outer pipe.
1.
Locate the power vent termination following
the clearance to combustible table, venting
configuration diagram (Fig. #2 & 3), and
terminal location diagram (Fig. #1).
2.
Cut and frame an 11" x 11" opening. The center
of the square hole should line up with the
center
3.
Install the M&G Duravent (or equivalent) Wall
thimble, part number 46DVA-WT (not supplied
with kit) in the opening to retain any insulation
in the wall and maintain proper clearances. If
the wall being penetrated is constructed of
noncombustible material only (i.e., Masonry
block or concrete) the wall thimble is not
required and a hole with zero clearance is
acceptable. (6 5/8” hole)
Figure #4
4.
Attach the terminal to the outside wall. Ensure that the terminal is the right way up and that only
the outer flanges that are used to secure the terminal to the building are covered by the exterior
wall or siding. (Fig.#4)
Note: No other part of the terminal can be recessed into the exterior
wall or siding.
5.
Attach the vent adaptor directly to the appliance after the initial 45
⁰
elbow before any
horizontal or vertical pipe is added. Tape all exterior seams on the venting system with foil HVAC
tape.
Note: The inner pipe does not need to be sealed.
(Fig. #5)
6.
Connect the high temperature silicone tube to the vacuum pressure tap on the adaptor, secure
with the hose clamp provided and route the tube through the utility access panel back to Power
vent control location. (Fig. #5) Tube may touch unit and be trimmed if required. Connect the
pressure switch tubing to the light grey port on the power vent control. Note: Ensure that there
are no blockages in this tube, as this will cause the control to malfunction. Do not allow tube to
rest on firebox after it is routed.
7.
Run the required Simpson Duravent GS / Secure Vent / Selkirk Direct-temp pipe from the adaptor
to the terminal assembly. Assemble as per the vent pipe manufacturer’s instructions.
Содержание PV-800HZ
Страница 5: ...4...
Страница 8: ...7 Figure 5...
Страница 10: ...9 11 With the power vent terminal resting on the drip shield align the eight holes in...
Страница 11: ...10 VERTICAL THROUGH ROOF VENTING Final Installation Height 21 Figure 6...
Страница 15: ...14 Disconnect the Red TC spade connector...
Страница 20: ...19...
Страница 21: ...20 V1 2 26 16...