POWER VENT CLEARANCES 

 

 

Figure #1 

 

A.

 

clearances above grade, veranda, porch, deck, or balcony [*12 inches (30 cm) minimum] 

B.

 

clearance to window or door that may be opened [* 12 inches (30 cm) minimum] 

C.

 

clearance to permanently closed window [minimum 12 inches (30 cm) recommended to prevent condensation on 

window] 

D.

 

vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (60 cm) from the 

edge of the terminal [12 inches (30 cm) minimum] 

E.

 

clearance to unventilated soffit [12 inches (30 cm) minimum] 

F.

 

clearance to outside corner [6 inches (15 cm) minimum] 

G.

 

clearance to inside corner [6 inches (15 cm) minimum] 

H.

 

* not to be installed above a meter/regulator assembly within 3 feet (90 cm) horizontally from the center-line of the 
regulator 

I.

 

clearance to service regulator vent outlet [* 6 feet (1.8 m) minimum] 

J.

 

clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance [* 12 

inches (30 cm) minimum] 

K.

 

clearance to a mechanical air supply inlet [* 6 feet (1.8 m) minimum] 

L.

 

^ clearance above paved side-walk or a paved driveway located on public property [* 7 feet (2.1 m) minimum] 

M.

 

clearance under veranda, porch, deck, or balcony [12 inches (30 cm) minimum**] 

 
^ a vent shall not terminate directly above a side-walk or paved driveway which is located between two single family 

dwellings and serves both dwellings* 
** only permitted if veranda, porch, deck, or balcony is fully open on a minimum of 2 sides beneath the floor* 

* as specified in CGA B149 Installation Codes, Note: local Codes or Regulation may require different clearances 
* for U.S.A. Installations follow the current National Fuel Gas Code, NSI Z223.1 

 
 
 

Содержание PV-800HZ

Страница 1: ...S SEE THRU MODELS BI 48 ST BI 60 ST BI 72 ST SINGLE SIDE MODELS BI 48 SSL BI 48 SSR BI 60 SSL BI 60 SSR BI 72 SSL BI 72 SSR DIRECT VENT POWER VENT KIT PART PV 800HZ AND PV 850V Report 0361GF006S Ce ma...

Страница 2: ...cal Instructions 15 Replacement Parts List 16 Warranty Information 17 WE STRONGLY SUGGEST THAT YOU READ THIS MANUAL THOROUGHLY BEFORE BEGININNG THE INSTALLATION OF THE S LAS POWER VENT KIT THIS SPECIF...

Страница 3: ...D 804 POWER VENT CONTROL W PRESSURE SWITCH 1 10 HRD 852V OPTIONAL VERTICAL TERMINATION HARDWARE KIT 1 This kit uses either M G Duravent direct vent pipe Secure Vent direct vent pipe or Selkirk Direct...

Страница 4: ...rom the center line of the regulator I clearance to service regulator vent outlet 6 feet 1 8 m minimum J clearance to non mechanical air supply inlet to building or the combustion air inlet to any oth...

Страница 5: ...4...

Страница 6: ...ion of rise and run between the figures including up to 3 ft below the unit Figure 2 WARNING A minimum clearance to combustibles of 1 5 38mm is required around the vent pipe at all times Failure to ma...

Страница 7: ...he outer flanges that are used to secure the terminal to the building are covered by the exterior wall or siding Fig 4 Note No other part of the terminal can be recessed into the exterior wall or sidi...

Страница 8: ...7 Figure 5...

Страница 9: ...time thread the electrical lead through the hole in the bottom of the terminal each side of the vertical standoff the drip shield and the power vent terminal and then screw them together using the eig...

Страница 10: ...9 11 With the power vent terminal resting on the drip shield align the eight holes in...

Страница 11: ...10 VERTICAL THROUGH ROOF VENTING Final Installation Height 21 Figure 6...

Страница 12: ...essure switch requires a positive pressure of 0 05 W C to confirm the power vent is running There are 2 female connectors on the bottom surface of the power vent control enclosure as shown above The l...

Страница 13: ...ff the unit Connect the pressure tap on the vent adapter to the light grey port on the control using the pressure switch tubing HRD 806 provided Tape all seams in the venting system using Aluminum Foi...

Страница 14: ...the power vent relay harness HRD 803 to the AUX port on the fireplace control Connect the red wire spade connector from the power vent relay harness HRD 803 Cut the Red TC spade connector off Crimp o...

Страница 15: ...14 Disconnect the Red TC spade connector...

Страница 16: ...e fireplace is enclosed WARNING All electrical shall be completed by a licensed Electrician and must conform with local building code Improper installation may result in property damage injury or loss...

Страница 17: ...TIONAL VERTICAL TERMINATION CAP 1 4 HRD 803 POWER VENT RELAY HARNESS 1 9 HRD 851V OPTIONAL VERTICAL TERMINATION BOX 1 5 HRD 804 POWER VENT CONTROL W PRESSURE SWITCH 1 10 HRD 852V OPTIONAL VERTICAL TER...

Страница 18: ...Over firing operation above the listed BTU rate of this appliance can cause serious damage and will nullify this warranty This warranty is void if a The unit has been operated in atmospheres contamin...

Страница 19: ...18 c Any damage to the unit combustion chamber heat exchanger or other components due to water or weather damage which is the result of but not limited to improper chimney venting installation...

Страница 20: ...19...

Страница 21: ...20 V1 2 26 16...

Отзывы: